Relay Output Output Channel 8
Contact Type Form A : normal open (N.O.) contact
Contact Rating 5A@250VAC or 5A@30VDC
Operate/Release Time 6mS/3mS max.
Life Mechanical : 2*107 min.
Electrical : 105 min. (Contact Rating)
Dielectric Strength between open contacts : 750VAC
between coil and contacts : 2000VAC
Surge Strength 4000V
LED Display 1 LED as Power/Communication indicator
8 LEDs as relay output indicators
Power Consumption Maximum : 1.7W


i-87064 pin assignment
Terminal Number Pin Name
1NO0
2COM0
3NO1
4COM1
5-
6NO2
7COM2
8NO3
9COM3
10-
11NO4
12COM4
13NO5
14COM5
15-
16NO6
17COM6
18NO7
19COM7
20-


i-87064 block diagram


Output Type ON State
LED ON
Readback as 1
OFF State
LED OFF
Readback as 0
Relay Contact
load current on i-87064 relay contact
load current off i-87064 relay contact


i-87064 dimention


Configuration Default Setting Description
Type 40 Digital Input/Output
Baudrate 0A 115200 bps
Format 00 CheckSum disable


Command Description
%AANNTTCCFF Set Module Configuration
$AA2 Read module configuration
$AA4 Read synchronized digital input/output status
$AA5 Read reset status
$AA6 Read digital input/output status
$AAF Read firmware version
$AAM Read module name
#** Synchronized sampling
#AABBDD Digital output
@AA Read digital input/output status
@AA(Data) Set digital outputs
~AA0 Read module status
~AA1 Reset module status
~AA2 Read host watchdog timeout setting
~AA3ETT Set host watchdog timeout setting
~AA4S Read PowerOn Value / Safe Value
~AA5S Set PowerOn Value / Safe Value
~AAO(Name) Set module name


Back to Previous Page