[U(mV)-T(°C) calibration]
FitMethod = Polynom
TransformX = Line
TransformY = CALC_TC_T
Power = 1
Center = 0
Scale = 1
Fixed = 1
Coeff[0] = 0
Coeff[1] = 1
Bounds = -6.258 20.872
Data U(mV)  T(°C)  Weight Tcj(°C)
     -6.258 -270   1      0
     -6.180 -250   1      0
     -5.950 -225   1      0
     -5.603 -200   1      0
     -5.167 -175   1      0
     -4.648 -150   1      0
     -4.052 -125   1      0
     -3.379 -100   1      0
     -2.633 -75    1      0
     -1.819 -50    1      0
     -0.940 -25    1      0
     0.000  0      1      0
     0.992  25     1      0
     2.036  50     1      0
     3.132  75     1      0
     4.279  100    1      0
     5.470  125    1      0
     6.704  150    1      0
     7.977  175    1      0
     9.288  200    1      0
     10.634 225    1      0
     12.013 250    1      0
     13.423 275    1      0
     14.862 300    1      0
     16.327 325    1      0
     17.819 350    1      0
     19.335 375    1      0
     20.872 400    1      0
End Data
Notice Text
Standard calibration of thermocouple type T (Cu/Cu-45%Ni) ТМКн медь/константан copper/constantan
Reference source: GOST R 8.585—2001, Table 5; IEC 60584-1(1995)
Configuration example:
Link AnalogInput  0 with curve ThermoCoupleVoltage(mV)
Link AnalogInput  1 with curve TemperatureColdJunction(°C)
Link AnalogOutput 0 with curve TemperatureThermoCouple(°C) history 100
Calibration#0 = ~~\Resource\DaqSite\StdLib\Calibr\_CALC_TC_T.CAL U(mV) T(°C) Tcj(°C) Line CALC_TC_T -6.258 20.872
End Notice Text