AliPhosCool: Help on Emerson EC3-X32 controller


Abstract

CERN ALICE PHOS detector's cooling plant (named AliPhosCool) includes Emerson EC3-X32 controller to control freon flow by using ECV (Electrical Control Valve) of type EX4. This document describe the controller and containts some important technical information about controller to use for cooling system.


Content

  • Open help index, directory.
  • Login to connect EC3-X32 controller.
  • Screensots: 1 2 3 4 5 6 7 8 to set EC3-X32 controller parameters.
  • Brief Saved configuration to Upload parameters.
  • Brief Brief info.
  • Short Short Short manual.
  • Brief TCP/IP manual
  • ECV selection tools to find optimal ECV configuration.
  • Protocol to monitor controller state via TCP/IP port.
  • Visit Emerson home site to find more information.
EC3-X32 view

Login to connect EC3-X32 controller

First, login to alidcscom252 (cooling plant server) via Remote Desktop (User:daq Pass:123).
Then open Web Browser (Internet Explorer or FireFox) to connect to EC3-X32 controller with next account:

Note that controller connected to alidcscom252 server via LAN-2 network (LAN-1 uses for Internet connection).

Just for information:

   ipconfig /all
   
   Настройка протокола IP для Windows
        Имя компьютера  . . . . . . . . . : alidcscom252
        Основной DNS-суффикс  . . . . . . : cern.ch
        Тип узла. . . . . . . . . . . . . : одноранговый
        IP-маршрутизация включена . . . . : нет
        WINS-прокси включен . . . . . . . : нет
        Порядок просмотра суффиксов DNS . : cern.ch
                                            cern.ch
                                            
   Подключение по локальной сети 2 - Ethernet адаптер:
        DNS-суффикс этого подключения . . : 
        Описание  . . . . . . . . . . . . : Intel(R) PRO/100 M Desktop Adapter #2
        Физический адрес. . . . . . . . . : 00-10-F3-11-F7-AD
        Dhcp включен. . . . . . . . . . . : нет
        IP-адрес  . . . . . . . . . . . . : 192.168.0.1
        Маска подсети . . . . . . . . . . : 255.255.255.0
        Основной шлюз . . . . . . . . . . : 

   Подключение по локальной сети - Ethernet адаптер:
        DNS-суффикс этого подключения . . : cern.ch
        Описание  . . . . . . . . . . . . : Intel(R) PRO/100 M Desktop Adapter
        Физический адрес. . . . . . . . . : 00-10-F3-11-F7-AC
        Dhcp включен. . . . . . . . . . . : да
        Автонастройка включена  . . . . . : да
        IP-адрес  . . . . . . . . . . . . : 10.160.128.20
        Маска подсети . . . . . . . . . . : 255.255.0.0
        Основной шлюз . . . . . . . . . . : 10.160.1.1
        DHCP-сервер . . . . . . . . . . . : 137.138.16.9
        DNS-серверы . . . . . . . . . . . : 137.138.16.5
                                            137.138.17.5
        Основной WINS-сервер  . . . . . . : 137.138.16.248
        Дополнительный WINS-сервер. . . . : 137.138.17.248
        Аренда получена . . . . . . . . . : 30 апреля 2008 г. 14:37:23
        Аренда истекает . . . . . . . . . : 7 мая 2008 г. 14:37:23
  

goto Content


Screenshots to set EC3-X32 controller parameters

Important note: In normal operation mode Digital Input should be ON (24 V).
In this mode most parameters may be changed.
But to change pressure sensor, refregerant, and valve type Digital Input should be OFF (O V).

  1. Monitor page (no password required).
    Monitor page

  2. Alarm page (no password required).
    Alarm page

  3. Service page (password required).
    Service page

  4. I/O configuration page (password required).
    I/O configuration page

  5. Superheat page (password required).
    Superheat page

  6. Pressure page (password required).
    Pressure page

  7. Display page (password required).
    Display page

  8. TCP/IP page (password required).
    TCP/IP page

goto Content


Protocol to monitor EC3-X32 controller state via TCP/IP port

   Emerson monitor protocol description:
   -------------------------------------
   1)Open TCP port 1030 as client.
   2)Send message "page 0\0" to controller (i.e. 'page 0'+Chr(0) on Pascal).
   3)Reply will be long ampersand-separated string looks like that:
     nvomo01=4.29&nvomo02=6.25&nvomo03=10.25&nvomo04=29.37&nvomo05=-3.92&
     nvomo06=1&nvomo07=2&nvomo08=26&nvomo09=29&nvomo10=11&nvomo11=2000&nvomo12=1&
     nvomo13=1&nvomo14=-1&nvomo15=10.0&nvomo16=0&nvomo17=4&nvomo18=129&
   4)Ampersand (&) separated fields are:
     Name    | Description              | Units
     -----------------------------------------------
     nvomo01 | Suction pressure         | bar
     nvomo02 | Suction gas temperature  | °C
     nvomo03 | Superheat                | K
     nvomo04 | Valve opening            | %
     nvomo05 | Evaporating temperature  | °C
     nvomo06 | Digital inputs           | 1: Cooling demand
     nvomo07 | Digital outputs          | 1: Alarm, 2:Compressor
     nvomo08 | ?                        | ?
     nvomo09 | ?                        | ?
     nvomo10 | ?                        | ?
     nvomo11 | ?                        | ?
     nvomo12 | ?                        | ?
     nvomo13 | ?                        | ?
     nvomo14 | ?                        | ?
     nvomo15 | Superheat setpoint       | K
     nvomo16 | ?                        | ?
     nvomo17 | ?                        | ?
     nvomo18 | ?                        | ?
   

See also some Emerson Java scripts there.

goto Content


AliPhosCool Alice Phos Cooling system CERN ALICE PHOS + VNIIEF 2009 Geneve,Switzerland + Sarov,Russia Alexei.Kuryakin@cern.ch