AliPhosCool: Help on ELMB


Abstract

The Embedded Local Monitor Board (ELMB) is a general-purpose plug-on I/O module for the monitoring and control of subdetector front-end equipment. The ELMB is based on the industry standard CANbus and CANopen has been implemented as high-level communication protocol. Kvaser CAN bus card and OPC server uses to connect ELMB to control computer.


Content

ELMB view

ELMB installation

  1. Install KVASER PCI CAN card in PCI slot.
    Before installation, set switches, see manual.
  2. Install KVASER PCI CAN card drivers for Windows-2k/XP, see manual.
  3. Connect CAN cable from KVASER card to CAN on ELMB.
    Connector DB9, 3-wire cable, 2<-->2, 3<-->3, 7<-->7 pins.
  4. Connect ELMB power. Two 10..12V, 200mA power supply needed.
    First -(VAG,VDG),+(VAP,VDP), second -VCG,+VCP. See manual.
  5. Set ELMB switch to baidrate 12500, wanted address, see manual.
  6. Install OPC core components, if one not installed.
  7. Install CAN Open OPC server, see Setup.exe.
  8. Edit (if need) OPCCanServer.cfg file. You have to edit CAN BUS port number and ELMB address.
After that you are ready to load and start DAQ configuration !AliPhosCool.cfg.

goto Content


Practical notes

ELMB_DRV device produce curves like CAN_BUS_1.ELMB_01.ai_0..64. It's ADC mV.
ELMB_RvsT converts 64 ADC's mV to 32 resistance PHOS_MODULE_1.R_0..32 as R0=Rs*ADC1/ADC0.
ELMB_Ni100 converts resistance to Temperature in Celsius. To calibrate sensors, you have to change Ni100_*.cal calibration files.

goto Content


AliPhosCool Alice Phos Cooling system CERN ALICE PHOS + VNIIEF 2009 Geneve,Switzerland + Sarov,Russia Alexei.Kuryakin@cern.ch