AliPhosCool: Help on public tags


Abstract

AliPhosCool is cooling system for CERN ALICE PHOS detector.

This document describe public tags and DIM services of the cooling system.


Content

PHOS logo

List of public cooling system tags

Type Name of tag Comment information
Char[] PHOS.COOL.CLICK Remote click information (for remote clients).
Char[] PHOS.COOL.NOTIFY Remote click notification (for remote clients).
Char[] PHOS.COOL.ALARM_LOG Message on alarm (Interlock). It contains semicolon-separated lines which exlain reason of Interlock if one happened. This message is also to be saved into PHOS_DATA\ALARM.LOG log-file. For example:
INTERLOCK FROM ALIDCSCOM252;TIME: 2009.10.20-10:08:04;REASON: PUMP1  by TPMAX.;ACTION: COOLING SYSTEM HALTED FOR SAFETY;;
Char[] PHOS.COOL.CONSOLE Console for incoming commands.
Double PHOS.COOL.HOST_TIME Server (alidcscom252) time, milliseconds since Xmas (01.01.01-00:00:00). Updates each second.
Char[] PHOS.COOL.HOST_INFO Server (alidcscom252) date-time pid@hostname, like 2009.10.11-15:30:00 346@ALIDCSCOM252. Updates each second.
Double PHOS.COOL.P1 Pressure sensor in Condensing tube, Bar (absolute).
Double PHOS.COOL.P2 Pressure sensor in Evaporating (suction) tube, Bar (absolute).
Double PHOS.COOL.P3 Pressure sensor in cooling liquid (C6F14) pipe, Bar (absolute).
Double PHOS.COOL.T1 Temperature of cooling liguid (C6F14) output (penal in small tank), °C. Pt-100 RTD sensor PTB_05. That is main feedback parameter to control liquid temperature.
Double PHOS.COOL.T2 Temperature of cooling liguid (C6F14) output (penal in small tank), °C. Pt-100 RTD sensor PTB_06. That is reserved feedback parameter to control liquid temperature.
Double PHOS.COOL.T3 Temperature of cooling liquid (C6F14) in Receiver (big tank), °C.
Double PHOS.COOL.T4 Temperature of Heater 1, °C. Pt-100 RTD sensor PTS_10.
Double PHOS.COOL.T5 Temperature of Air inside cooling machine cover, °C. PTC sensor CARNO_T5.
Double PHOS.COOL.T6 Temperature of Control unit inside cooling machine, °C. ADAM4 cold junction.
Double PHOS.COOL.T7 Temperature of freon evaporating, °C. Calculated by P2 via R404A table.
Double PHOS.COOL.T8 Temperature of Pump1 cover, °C. Pt-100 RTD sensor PTS_42.
Double PHOS.COOL.T9 Temperature of Pump2 cover, °C. Pt-100 RTD sensor PTS_03.
Double PHOS.COOL.T10 Temperature of Air inside pump station cover, °C. ADAM6 cold junction.
Double PHOS.COOL.T11 Temperature °C of compressor 1 cover, °C. Pt-100 RTD sensor PTS_20.
Double PHOS.COOL.T12 Temperature °C of compressor 2 cover, °C. Ni-100 RTD sensor 0070.
Double PHOS.COOL.T13 Temperature °C of compressor 3 cover, °C. Ni-100 RTD sensor 0063.
Double PHOS.COOL.T14 Temperature °C of compressor 4 cover, °C. Ni-100 RTD sensor 0045.
Double PHOS.COOL.T15 Temperature °C of PHOS input pipeline. Pt-100 RTD sensor PTS_06.
Double PHOS.COOL.T16 Temperature °C of PHOS output pipeline. Pt-100 RTD sensor PTS_09.
Double PHOS.COOL.T17 Temperature of freon condensing, °C. Calculated by P1 via R404A table.
Double PHOS.COOL.T18 Temperature output-input difference, °C. Calculated as T16-T15.
Double PHOS.COOL.T19 Temperature output-input difference, °C. Calculated as T3-T1.
Double PHOS.COOL.T20 Temperature of pump ¹2 motor cover, °C.
Double PHOS.COOL.T21 Temperature of pump ¹1 motor cover, °C.
Double PHOS.COOL.T22 Temperature difference, °C, of cradle output - input, by sensors PWO3.T_10 - PWO3.T_11.
Integer PHOS.COOL.COMP1.ENB Compressor ¹ 1 enable/disable (1/0).
Integer PHOS.COOL.COMP1.POW Compressor ¹ 1 power on/off (1/0).
Double PHOS.COOL.COMP1.WTM Compressor ¹ 1 working time (summary). Compressors works in round-robin order to equalize working times.
Integer PHOS.COOL.COMP1.THR Compressor ¹ 1 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm.
Integer PHOS.COOL.COMP1.OIL Compressor ¹ 1 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm.
Integer PHOS.COOL.COMP1.LPR Compressor ¹ 1 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure.
Integer PHOS.COOL.COMP1.HPR Compressor ¹ 1 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure.
Integer PHOS.COOL.COMP2.ENB Compressor ¹ 2 enable/disable (1/0).
Integer PHOS.COOL.COMP2.POW Compressor ¹ 2 power on/off (1/0).
Double PHOS.COOL.COMP2.WTM Compressor ¹ 2 working time (summary). Compressors works in round-robin order to equalize working times.
Integer PHOS.COOL.COMP2.THR Compressor ¹ 2 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm.
Integer PHOS.COOL.COMP2.OIL Compressor ¹ 2 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm.
Integer PHOS.COOL.COMP2.LPR Compressor ¹ 2 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure.
Integer PHOS.COOL.COMP2.HPR Compressor ¹ 2 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure.
Integer PHOS.COOL.COMP3.ENB Compressor ¹ 3 enable/disable (1/0).
Integer PHOS.COOL.COMP3.POW Compressor ¹ 3 power on/off (1/0).
Double PHOS.COOL.COMP3.WTM Compressor ¹ 3 working time (summary). Compressors works in round-robin order to equalize working times.
Integer PHOS.COOL.COMP3.THR Compressor ¹ 3 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm.
Integer PHOS.COOL.COMP3.OIL Compressor ¹ 3 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm.
Integer PHOS.COOL.COMP3.LPR Compressor ¹ 3 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure.
Integer PHOS.COOL.COMP3.HPR Compressor ¹ 3 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure.
Integer PHOS.COOL.COMP4.ENB Compressor ¹ 4 enable/disable (1/0).
Integer PHOS.COOL.COMP4.POW Compressor ¹ 4 power on/off (1/0).
Double PHOS.COOL.COMP4.WTM Compressor ¹ 4 working time (summary). Compressors works in round-robin order to equalize working times.
Integer PHOS.COOL.COMP4.THR Compressor ¹ 4 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm.
Integer PHOS.COOL.COMP4.OIL Compressor ¹ 4 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm.
Integer PHOS.COOL.COMP4.LPR Compressor ¹ 4 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure.
Integer PHOS.COOL.COMP4.HPR Compressor ¹ 4 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure.
Integer PHOS.COOL.PUMP1.ENB Pump ¹ 1 enable/disable (1/0). Disabled pump can't be powered on.
Integer PHOS.COOL.PUMP1.POW Pump ¹ 1 power on/off (1/0).
Double PHOS.COOL.PUMP1.WTM Pump ¹ 1 working time (summary). Pumps works in round-robin order to equalize working times.
Integer PHOS.COOL.PUMP1.THR Pump ¹ 1 thermo relay on/off (1/0). This signal means pump overload and may cause alarm.
Integer PHOS.COOL.PUMP2.ENB Pump ¹ 2 enable/disable (1/0). Disabled pump can't be powered on.
Integer PHOS.COOL.PUMP2.POW Pump ¹ 2 power on/off (1/0).
Double PHOS.COOL.PUMP2.WTM Pump ¹ 2 working time (summary). Pumps works in round-robin order to equalize working times.
Integer PHOS.COOL.PUMP2.THR Pump ¹ 2 thermo relay on/off (1/0). This signal means pump overload and may cause alarm.
Integer PHOS.COOL.FREON.ENB Freon (R404A) vent Y1 enable/disable (1/0). Disabled vent can't be powered on.
Integer PHOS.COOL.FREON.VE1 Freon (R404A) solenoid vent power on/off (1/0). Vent opening enables freon flow.
Integer PHOS.COOL.FREON.LPR Low freon (R404A) pressure relay on/off. This signal means lack of freon and may cause alarm. Possible reason - freon leak.
Integer PHOS.COOL.FREON.HPR High freon (R404A) pressure relay. This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure.
Integer PHOS.COOL.FREON.ECV ECV state. 0 means Ok. Otherwise Bit0=NotOk, Bit1=Alarm, Bit2=TimeOut. ECV is Electrical Control Valve with Emerson controller EC3-X32 to control freon (R404A) flow.
Integer PHOS.COOL.FREON.POWER Indicate presence of genegal power (380V) for cooling machine (1=ON,0=OFF).
Integer PHOS.COOL.FREON.WATER Indicate presence of water cooling (1=ON,0=OFF).
Calculated like that:
if((PHOS.COOL.WATER.FLOW≥PHOS.COOL.WATER.FEDGE)
or (PHOS.COOL.P1<PHOS.COOL.WATER.PEDGE))
then PHOS.COOL.FREON.WATER:=1 else PHOS.COOL.FREON.WATER:=0.
Double PHOS.COOL.WATER.FLOW Indicate water flow rate, Liters per minute.
Double PHOS.COOL.WATER.FEDGE Threshold for water flow rate to detect WATER, see PHOS.COOL.FREON.WATER.
Double PHOS.COOL.WATER.PEDGE Threshold for P1 to detect WATER, see PHOS.COOL.FREON.WATER.
Integer PHOS.COOL.LIQ.ENB Cooling liquid (C6F14) vent Y2 enable/disable (1/0). Disabled vent could not be powered on.
Integer PHOS.COOL.LIQ.VE2 Cooling liquid (C6F14) solenoid vent Y1 power on/off (1/0).
Integer PHOS.COOL.LIQ.HLR Cooling liquid (C6F14) high level relay on/off (1/0). This signal means liquid overpressure and may cause alarm. Possible reason - thrombus in pipes.
Integer PHOS.COOL.LIQ.LLR Cooling liquid (C6F14) low level relay on/off (1/0). This signal means lack of liquid and may cause alarm. Possible reason - liquid leak.
Integer PHOS.COOL.LIQ.REED 4-bit state of 4 reed switches of liquid level. Bit 0 means empty receiver tank, bit 3 - full tank.
Double PHOS.COOL.LIQ.TMIN Cooling liquid (C6F14) temperature low level,°C. Uses to generate alarm on cooling liquid temperature.
Double PHOS.COOL.LIQ.TMAX Cooling liquid (C6F14) temperature high level,°C. Uses to generate alarm on cooling liquid temperature.
Double PHOS.COOL.LIQ.TSTAB Cooling liquid (C6F14) nominal ("wanted") stabilization temperature,°C. Note that actual ("applied") stabilization temperature PHOS.COOL.LIQ.TGOAL also depends on PHOS.COOL.LIQ.DTMAX and current PWO temperature PHOS.COOL.LIQ.TSENS (to avoid PWO damage due to temperature gradient).
Double PHOS.COOL.LIQ.DELTA Cooling liquid (C6F14) temperature stabilization corridor,°C. Compressor(s) turn on/off temperature = TGOAL ± DELTA.
Integer PHOS.COOL.LIQ.NBSEN This tag define which sensor (i.e. PHOS module number in 0..4 range) uses for control cooling speed. This sensor uses to calculate PHOS.COOL.LIQ.TSENS.
Double PHOS.COOL.LIQ.DTMAX Maximal temperature difference for cooling speed control,°C. Uses to calculate "applied" stabilization temperature PHOS.COOL.LIQ.TGOAL.
Double PHOS.COOL.LIQ.TSENS Current PWO sensor (by PHOS.COOL.LIQ.NBSEN) temperature,°C. Uses to calculate "applied" stabilization temperature PHOS.COOL.LIQ.TGOAL.
Double PHOS.COOL.LIQ.TGOAL Current actual ("applied") cooling liquid (C6F14) stabilization ("goal") temperature,°C.
Compressor(s) turn on/off temperature = TGOAL ± DELTA.
TGOAL calculates by TSTAB with condition ABS(TSENS-TGOAL)<=DTMAX.
If ABS(TSENS-TSTAB)<=DTMAX or DTMAX=0, then TGOAL=DTMAX.
Otherwise TGOAL=MIN(TSENS+DTMAX,MAX(TSENS-DTMAX,TSTAB)).
This condition guarantee limited temperature gradient to avoid PWO damage.
Double PHOS.COOL.LIQ.TAVER Current cooling liquid (C6F14) average (over control cycle) temperature,°C.
Double PHOS.COOL.LIQ.CAVER Current average control cycle period, minutes (see picture above).
Double PHOS.COOL.LIQ.NAVER Current average number of working compressors per cycle. It's proportional to average cooling power per cycle.
Integer PHOS.COOL.LIQ.NCOMP Current number of working compressors (0..4).
Double PHOS.COOL.LIQ.LLS.MM Current cooling liquid (C6F14) level in receiver tank, mm.
Double PHOS.COOL.LIQ.LLS.PC Current cooling liquid (C6F14) level in receiver tank, % of tank volume (65L).
Double PHOS.COOL.LIQ.LLS.VL Current cooling liquid (C6F14) level in receiver tank, liters.
Double PHOS.COOL.LIQ.LLS.LO Low cooling liquid (C6F14) level threshold for alarm, Liters.
Double PHOS.COOL.LIQ.LLS.HI High cooling liquid (C6F14) level threshold for alarm, Liters.
Integer PHOS.COOL.LIQ.NFDBK Number of feedback sensor, 1=T1, 2=T2, 3=T1 and T2. This number define, which sensor uses to calculate feedback temperature for stabilization.
Double PHOS.COOL.LIQ.TFDBK Temperature of feedback sensor, T1 or T2 or (T1+T2)/2.
Integer PHOS.COOL.FAN.ENB Fan enable/disable (1/0). Disabled fan can't be powered on.
Integer PHOS.COOL.FAN.POW Fan power on/off (1/0).
Double PHOS.COOL.FAN.WTM Fan working time (summary), hours.
Double PHOS.COOL.FAN.TON Fan turn on temperature, °C.
Integer PHOS.COOL.FAN1.ENB Fan1 (pump 1 inflow and outflow) enable/disable (1/0). Disabled fan can't be powered on.
Integer PHOS.COOL.FAN1.POW Fan1 (pump 1 inflow and outflow) power on/off (1/0).
Integer PHOS.COOL.FAN2.ENB Fan2 (pump 2 inflow and outflow) enable/disable (1/0). Disabled fan can't be powered on.
Integer PHOS.COOL.FAN2.POW Fan2 (pump 2 inflow and outflow) power on/off (1/0).
Integer PHOS.COOL.FAN3.ENB Fan3 (compressor station outflow) enable/disable (1/0). Disabled fan can't be powered on.
Integer PHOS.COOL.FAN3.POW Fan3 (compressor station outflow) power on/off (1/0).
Integer PHOS.COOL.FAN4.ENB Fan4 (compressor station inflow) enable/disable (1/0). Disabled fan can't be powered on.
Integer PHOS.COOL.FAN4.POW Fan4 (compressor station inflow) power on/off (1/0).
Integer PHOS.COOL.HEAT1.ENB Heat ¹ 1 enable/disable (1/0).
Integer PHOS.COOL.HEAT1.POW Heat ¹ 1 power on/off (1/0).
Integer PHOS.COOL.HEAT1.SSR Heat ¹ 1 solid state relay on/off (1/0).
Integer PHOS.COOL.HEAT1.PER Heat ¹ 1 period, ms.
Double PHOS.COOL.HEAT1.Q Heat ¹ 1 power, %. 100% correspond to 1 kW. T4 uses to control heater temperature
Double PHOS.COOL.HEAT1.QMAX Heat ¹ 1 maximal power, %.
Integer PHOS.COOL.HEAT2.ENB Heat ¹ 2 enable/disable (1/0).
Integer PHOS.COOL.HEAT2.POW Heat ¹ 2 power on/off (1/0).
Integer PHOS.COOL.HEAT2.SSR Heat ¹ 2 solid state relay on/off (1/0).
Integer PHOS.COOL.HEAT2.PER Heat ¹ 2 period, ms.
Double PHOS.COOL.HEAT2.Q Heat ¹ 2 power, %.
Double PHOS.COOL.HEAT2.QMAX Heat ¹ 2 maximal power, %.
Integer PHOS.COOL.HEAT3.ENB Heat ¹ 3 enable/disable (1/0).
Integer PHOS.COOL.HEAT3.POW Heat ¹ 3 power on/off (1/0).
Integer PHOS.COOL.HEAT3.SSR Heat ¹ 3 solid state relay on/off (1/0).
Integer PHOS.COOL.HEAT3.PER Heat ¹ 3 period, ms.
Double PHOS.COOL.HEAT3.Q Heat ¹ 3 power, %.
Double PHOS.COOL.HEAT3.QMAX Heat ¹ 3 maximal power, %.
Double PHOS.COOL.COMP.P1MIN Minimal condensator pressure, Bar. Threshold for alarms.
Double PHOS.COOL.COMP.P1MAX Maximal condensator pressure, Bar. Threshold for alarms.
Double PHOS.COOL.COMP.P2MIN Minimal evaporating pressure, Bar. Threshold for alarms.
Double PHOS.COOL.COMP.P2MAX Maximal evaporating pressure, Bar. Threshold for alarms.
Integer PHOS.COOL.COMP.NBMIN Minimal number of working compressors.
Integer PHOS.COOL.COMP.NBMAX Maximal number of working compressors.
Double PHOS.COOL.COMP.POLLTM Polling period, seconds.
Double PHOS.COOL.COMP.DEADTM Dead time after on/off, seconds.
Double PHOS.COOL.COMP.TCMIN Minimal compressor cover temperature,°C. Threshold for alarms.
Double PHOS.COOL.COMP.TCMAX Maximal compressor cover temperature,°C. Threshold for alarms.
Double PHOS.COOL.COMP.CYCLE Compressor shift cycle, hours.
Double PHOS.COOL.PUMP.P3MIN Minimal pressure liquid limit, Bar. Threshold for alarms.
Double PHOS.COOL.PUMP.P3MAX Maximal pressure liquid limit, Bar. Threshold for alarms.
Double PHOS.COOL.PUMP.TPMIN Minimal pump body (cover) temperature, °C. Threshold for alarms.
Double PHOS.COOL.PUMP.TPMAX Maximal pump body (cover) temperature, °C. Threshold for alarms.
Double PHOS.COOL.PUMP.CYCLE Pump shift cycle, hours.
Double PHOS.COOL.HEATS.T4MAX High T4 heater ¹1 limit, °C. Threshold for alarms.
Double PHOS.COOL.STBY.TSTAB Liquid stabilization temperature (for STANDBY state), °C. This parameter copied to PHOS.COOL.LIQ.TSTAB when system going to STANDBY state.
Double PHOS.COOL.STBY.DELTA Temperature corridor (for STANDBY state). Compressor turn on/off temperature = TSTAB ± DELTA. This parameter copied to PHOS.COOL.LIQ.DELTA when system going to STANDBY state.
Integer PHOS.COOL.STBY.NBMIN Minimal number of working compressors (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.NBMIN when system going to STANDBY state.
Integer PHOS.COOL.STBY.NBMAX Maximal number of working compressors (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.NBMAX when system going to STANDBY state.
Double PHOS.COOL.STBY.POLLTM Polling period, seconds (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.POLLTM when system going to STANDBY state.
Double PHOS.COOL.STBY.DEADTM Dead time after on/off, seconds (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.DEADTM when system going to STANDBY state.
Integer PHOS.COOL.STBY.NBSEN Sensor number for cooling speed control (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.NBSEN when system going to STANDBY state.
Double PHOS.COOL.STBY.DTMAX Maximal temperature delta for cooling speed control,°C (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.DTMAX when system going to STANDBY state.
Double PHOS.COOL.STBY.Q1 Heat ¹1 power, % (for STANDBY state). This parameter copied to PHOS.COOL.HEAT1.Q when system going to STANDBY state.
Double PHOS.COOL.STBY.Q2 Heat ¹2 power, % (for STANDBY state). This parameter copied to PHOS.COOL.HEAT2.Q when system going to STANDBY state.
Double PHOS.COOL.STBY.Q3 Heat ¹3 power, % (for STANDBY state). This parameter copied to PHOS.COOL.HEAT3.Q when system going to STANDBY state.
Double PHOS.COOL.COOL.TSTAB Liquid stabilization temperature (for COOLING state), °C. This parameter copied to PHOS.COOL.LIQ.TSTAB when system going to COOLING state.
Double PHOS.COOL.COOL.DELTA Temperature corridor (for COOLING state). Compressor turn on/off temperature = TSTAB ± DELTA. This parameter copied to PHOS.COOL.LIQ.DELTA when system going to COOLING state.
Integer PHOS.COOL.COOL.NBMIN Minimal number of working compressors (for COOLING state). This parameter copied to PHOS.COOL.LIQ.NBMIN when system going to COOLING state.
Integer PHOS.COOL.COOL.NBMAX Maximal number of working compressors (for COOLING state). This parameter copied to PHOS.COOL.LIQ.NBMAX when system going to COOLING state.
Double PHOS.COOL.COOL.POLLTM Polling period, seconds (for COOLING state). This parameter copied to PHOS.COOL.LIQ.POLLTM when system going to COOLING state.
Double PHOS.COOL.COOL.DEADTM Dead time after on/off, seconds (for COOLING state). This parameter copied to PHOS.COOL.LIQ.DEADTM when system going to COOLING state.
Integer PHOS.COOL.COOL.NBSEN Sensor number for cooling speed control (for COOLING state). This parameter copied to PHOS.COOL.LIQ.NBSEN when system going to COOLING state.
Double PHOS.COOL.COOL.DTMAX Maximal temperature delta for cooling speed control,°C (for COOLING state). This parameter copied to PHOS.COOL.LIQ.DTMAX when system going to COOLING state.
Double PHOS.COOL.COOL.Q1 Heat ¹1 power, % (for COOLING state). This parameter copied to PHOS.COOL.HEAT1.Q when system going to COOLING state.
Double PHOS.COOL.COOL.Q2 Heat ¹2 power, % (for COOLING state). This parameter copied to PHOS.COOL.HEAT2.Q when system going to COOLING state.
Double PHOS.COOL.COOL.Q3 Heat ¹3 power, % (for COOLING state). This parameter copied to PHOS.COOL.HEAT3.Q when system going to COOLING state.
Double PHOS.COOL.WARM.TSTAB Liquid stabilization temperature (for WARMING state), °C. This parameter copied to PHOS.COOL.LIQ.TSTAB when system going to WARMING state.
Double PHOS.COOL.WARM.DELTA Temperature corridor (for WARMING state). Compressor turn on/off temperature = TSTAB ± DELTA. This parameter copied to PHOS.COOL.LIQ.DELTA when system going to WARMING state.
Integer PHOS.COOL.WARM.NBMIN Minimal number of working compressors (for WARMING state). This parameter copied to PHOS.COOL.LIQ.NBMIN when system going to WARMING state.
Integer PHOS.COOL.WARM.NBMAX Maximal number of working compressors (for WARMING state). This parameter copied to PHOS.COOL.LIQ.NBMAX when system going to WARMING state.
Double PHOS.COOL.WARM.POLLTM Polling period, seconds (for WARMING state). This parameter copied to PHOS.COOL.LIQ.POLLTM when system going to WARMING state.
Double PHOS.COOL.WARM.DEADTM Dead time after on/off, seconds (for WARMING state). This parameter copied to PHOS.COOL.LIQ.DEADTM when system going to WARMING state.
Integer PHOS.COOL.WARM.NBSEN Sensor number for cooling speed control (for WARMING state). This parameter copied to PHOS.COOL.LIQ.NBSEN when system going to WARMING state.
Double PHOS.COOL.WARM.DTMAX Maximal temperature delta for cooling speed control,°C (for WARMING state). This parameter copied to PHOS.COOL.LIQ.DTMAX when system going to WARMING state.
Double PHOS.COOL.WARM.Q1 Heat ¹1 power, % (for WARMING state). This parameter copied to PHOS.COOL.HEAT1.Q when system going to WARMING state.
Double PHOS.COOL.WARM.Q2 Heat ¹2 power, % (for WARMING state). This parameter copied to PHOS.COOL.HEAT2.Q when system going to WARMING state.
Double PHOS.COOL.WARM.Q3 Heat ¹3 power, % (for WARMING state). This parameter copied to PHOS.COOL.HEAT3.Q when system going to WARMING state.
Double PHOS.COOL.DAQ.BUGS DAQ error count. That is total number of Data Acquisition system errors (exclude OPC errors).
Double PHOS.COOL.COM.BUGS COM port errors. That is total number of errors in ADAM's RS-485 network (timeouts, CRC errors etc).
Integer PHOS.COOL.INTERLOCK Interlock on/off (1/0). Interlock means fatal error (failure) which can be dangerous for cooling plant. If interlock signal raised, cooling system execute HALT and switch off all control devices (pumps, compressors, valves), then send ALARM to DCS. Cooling can be started only after manual DCS user (shifter) RESET.
Integer PHOS.COOL.CMD.CTRL Current control mode.
CTRL=0 is OFF state. All devices switched OFF. It's absolutely safe state which correspond to FSM OFF state.
CTRL=1 is HAND (manual) mode. User can switch devices manually. Correspond to FSM CALIBRATION mode.
CTRL=2 is STANDBY mode. Y1, Y2 valves opened, but pumps, compressors is OFF. Correspond to FSM STANDBY mode.
CTRL=3 is COOLING mode. Main operation mode to detetor cooling. Correspond to FSM COOLING and READY mode.
CTRL=4 is WARMING mode. Uses for detector warming. Correspond to FSM WARMING state.
Integer PHOS.COOL.CMD.BLK Blocking (alarms) enable/disable (1/0). Alarms can be disabled only in HAND (manual) mode.
Integer PHOS.COOL.BLK.NUM Number (counter) of activeted blocks (alarms).
Integer PHOS.COOL.BLK.OPT1 Blocking options (1st part). Each bit enable/disable (1/0) some kind of alarm. Each alarm blocks some device (XXX) by some contition (YYY), so alarms named as "XXX by YYY". Each alarm has enable/disable flag, timeout and (maybe) option parameter, like threshold for alarm condition. Table of alarms listed below:
                          $00000001   VE1  by LPR   - freon vent by Lo pressure
                          $00000002   VE1  by HPR   - freon vent by Hi pressure
                          $00000004   PUMP by THR   - pump by thermo relay
                          $00000008   PUMP by VE2   - pump by liquid vent
                          $00000010   PUMP by LLR   - pump by Lo liquid level relay
                          $00000020   PUMP by HLR   - pump by Hi liquid level relay
                          $00000040   PUMP by P3MIN - pump by Lo liquid pressure
                          $00000080   PUMP by P3MAX - pump by Hi liquid pressure
                          $00000100   PUMP by TMIN  - pump by Lo liquid temperature
                          $00000200   PUMP by TMAX  - pump by Hi liquid temperature
                          $00000400   COMP by THR   - compressor by thermo relay
                          $00000800   COMP by OIL   - compressor by oil level sensor
                          $00001000   COMP by LPR   - compressor by Lo pressure relay
                          $00002000   COMP by HPR   - compressor by Hi pressure relay
                          $00004000   COMP by P1MIN - compressor by Lo P1 value
                          $00008000   COMP by P1MAX - compressor by Hi P1 value
                          $00010000   COMP by P2MIN - compressor by Lo P2 value
                          $00020000   COMP by P2MAX - compressor by Hi P2 value
                          $00040000   COMP by VE1   - compressor by freon vent
                          $00080000   COMP by PUMP  - compressor by pumps OFF
                          $00100000   HEAT by VE2   - heaters by liquid vent
                          $00200000   HEAT by PUMP  - heaters by pumps OFF
                          $00400000   HEAT by T4MAX - heaters by Hi T4 value
                          $00800000   HEAT by COMP  - heaters by compressors OFF
                          $01000000   PUMP by TPMIN - pump by Lo pump cover temp-re
                          $02000000   PUMP by TPMAX - pump by Hi pump cover temp-re
                          $04000000   VE1  by ADAMS - freon vent by ADAM errors
                          $08000000   LLR  by REED  - get LLR,HLR by reed swithes
                          $10000000   PUMP by LLSLO - pump by Lo Liquid Level Sensor
                          $20000000   PUMP by LLSHI - pump by Hi Liquid Level Sensor
                          $40000000   COMP by TCMIN - compressor by min. cover tempr
                          $80000000   COMP by TCMAX - compressor by max. cover tempr
                          
Integer PHOS.COOL.BLK.OPT2 Blocking options (2nd part, see above). Table of alarms listed below:
                           $00000001   COMP by ECV_NO - compressor by ECV NotOk
                           $00000002   COMP by ECV_AL - compressor by ECV ALarm
                           $00000004   COMP by ECV_TO - compressor by ECV TimeOut
                          
Double PHOS.COOL.ECV.nvomo01 ECV parameter: Suction pressure, Bar.
Double PHOS.COOL.ECV.nvomo02 ECV parameter: Suction gas temperature, °C.
Double PHOS.COOL.ECV.nvomo03 ECV parameter: Superheat, K.
Double PHOS.COOL.ECV.nvomo04 ECV parameter: Valve opening, %.
Double PHOS.COOL.ECV.nvomo05 ECV parameter: Evaporating temperature, °C.
Double PHOS.COOL.ECV.nvomo06 ECV parameter: Digital inputs, 1: Cooling demand.
Double PHOS.COOL.ECV.nvomo07 ECV parameter: Digital outputs, 1: Alarm, 2:Compressor.
Double PHOS.COOL.ECV.nvomo08 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo09 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo10 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo11 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo12 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo13 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo14 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo15 ECV parameter: Superheat setpoint, K.
Double PHOS.COOL.ECV.nvomo16 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo17 ECV parameter: at the moment, unknown.
Double PHOS.COOL.ECV.nvomo18 ECV parameter: at the moment, unknown.
Integer PHOS.COOL.WDT.VE1_LPR Alarm timeout: Block VE1 by LPR
This alarm blocks freon (R404A) vent Y1 if Low Pressure Relay connected during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: freon leak.
Integer PHOS.COOL.WDT.VE1_HPR Alarm timeout:Block VE1 by HPR
This alarm blocks freon (R404A) vent Y1 if High Pressure Relay connected during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: water cooling is off (no heat removed from water condensor).
Integer PHOS.COOL.WDT.PUMP_THR Alarm timeout: Block PUMP by THR
This alarm blocks pump (to flow C6F14) if THermo Relay connected during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: pump overload (overheat, overcurrent etc).
Integer PHOS.COOL.WDT.PUMP_VE2 Alarm timeout: Block PUMP by VE2
This alarm blocks pump (to flow C6F14) if Y2 vent (for cooling liquid) closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: pump switch on when Y2 vent closed (in manual mode). That is forbidden operation mode.
Integer PHOS.COOL.WDT.PUMP_LLR Alarm timeout: Block PUMP by LLR
This alarm blocks pump (to flow C6F14) if Low Level Relay closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: low level of cooling liquid in receiver tank (empty tank, liquid leak).
At the moment this relay doesn't work properly, so it's switched off.
Integer PHOS.COOL.WDT.PUMP_HLR Alarm timeout: Block PUMP by HLR
This alarm blocks pump (to flow C6F14) if High Level Relay closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: high level of cooling liquid in receiver tank (full tank, overload).
At the moment this relay doesn't work properly, so it's switched off.
Integer PHOS.COOL.WDT.PUMP_P3MIN Alarm timeout: Block PUMP by P3MIN
This alarm blocks pump (to flow C6F14) if liquid pressure less then threshold during timeout, i.e. P3 < P3min.
Negative timeout cause fatal Intelock.
Possible reason of alarm: no liquid (liquid leak) or sensor failure.
Integer PHOS.COOL.WDT.PUMP_P3MAX Alarm timeout: Block PUMP by P3MAX
This alarm blocks pump (to flow C6F14) if liquid pressure greater then threshold during timeout, i.e. P3 > P3max.
Negative timeout cause fatal Intelock.
Possible reason of alarm: closed vent or "thrombus" in cooling liqud's pipes or sensor failure.
Integer PHOS.COOL.WDT.PUMP_TMIN Alarm timeout: Block PUMP by TMIN
This alarm blocks pump (to flow C6F14) if liquid temperature less then threshold during timeout, i.e. T1 < Tmin.
Negative timeout cause fatal Intelock.
Possible reason of alarm: cooling liqud underheat (for example, wrong control parameter's setup).
Integer PHOS.COOL.WDT.PUMP_TMAX Alarm timeout: Block PUMP by TMAX
This alarm blocks pump (to flow C6F14) if liquid temperature greater then threshold during timeout, i.e. T1 > Tmax.
Negative timeout cause fatal Intelock.
Possible reason of alarm: cooling liqud overheat (for example, incufficient compressor's power).
Integer PHOS.COOL.WDT.COMP_THR Alarm timeout: Block COMP by THR
This alarm blocks compressor (to flow freon R404A) if THermo Relay closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: compressor overload (overheat, overcurrent etc).
Integer PHOS.COOL.WDT.COMP_OIL Alarm timeout: Block COMP by OIL
This alarm blocks compressor (to flow freon R404A) if OIL low level relay closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: compressor's oil low level (oil system failure or compressor frozen).
Integer PHOS.COOL.WDT.COMP_LPR Alarm timeout: Block COMP by LPR
This alarm blocks compressor (to flow freon R404A) if Low Pressure Relay closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: insufficient freon pressure (leak), freon ECV valve closed (with working compressors) or wrong control parameter's setup.
Integer PHOS.COOL.WDT.COMP_HPR Alarm timeout: Block COMP by HPR
This alarm blocks compressor (to flow freon R404A) if High Pressure Relay closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: freon overpressure due to freon overheat, when water condensor don't work (no water flow).
Integer PHOS.COOL.WDT.COMP_P1MIN Alarm timeout: Block COMP by P1MIN
This alarm blocks compressor (to flow freon R404A) if freon condensator (discharge) pressure less then threshold during timeout, i.e. P1 < P1min.
Negative timeout cause fatal Intelock.
Possible reason of alarm: insufficient freon pressure (leak).
Integer PHOS.COOL.WDT.COMP_P1MAX Alarm timeout: Block COMP by P1MAX
This alarm blocks compressor (to flow freon R404A) if freon evaporator (suction) pressure greater then threshold during timeout, i.e. P1 > P1max.
Negative timeout cause fatal Intelock.
Possible reason of alarm: freon overpressure due to freon overheat, when water condensor doesn't work (no water flow).
Integer PHOS.COOL.WDT.COMP_P2MIN Alarm timeout: Block COMP by P2MIN
This alarm blocks compressor (to flow freon R404A) if freon evaporator (suction) pressure less then threshold during timeout, i.e. P2 < P2min.
Negative timeout cause fatal Intelock.
Possible reason of alarm: insufficient freon pressure (leak), freon ECV valve closed (with working compressors) or wrong control parameter's setup.
Integer PHOS.COOL.WDT.COMP_P2MAX Alarm timeout: Block COMP by P2MAX
This alarm blocks compressor (to flow freon R404A) if freon evaporator (suction) pressure less then threshold during timeout, i.e. P2 > P2max.
Negative timeout cause fatal Intelock.
Possible reason of alarm: freon overpressure (for example, no water cooling).
Integer PHOS.COOL.WDT.COMP_VE1 Alarm timeout: Block COMP by VE1
This alarm blocks compressor (to flow freon R404A) if freon valve Y1 closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: compressor switch on when freon valve closed. This operation mode forbidden.
Integer PHOS.COOL.WDT.COMP_PUMP Alarm timeout: Block COMP by PUMP
This alarm blocks compressor (to flow freon R404A) if pump switched OFF during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: compressor switch on when pump is off. This operation mode forbidden.
Integer PHOS.COOL.WDT.HEAT_VE2 Alarm timeout: Block HEAT by VE2
This alarm blocks heater if cooling liquid valve Y2 closed during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: heater switch on when cooling liquid valve closed. This operation mode forbidden.
Integer PHOS.COOL.WDT.HEAT_PUMP Alarm timeout: Block HEAT by PUMP
This alarm blocks heater if pump switched OFF during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: heater switch on when pump is off. This operation mode forbidden.
Integer PHOS.COOL.WDT.HEAT_T4MAX Alarm timeout: Block HEAT by T4MAX
This alarm blocks heater 1 if T4 temperature is over threshold during timeout, i.e. T4 > T4max.
Negative timeout cause fatal Intelock.
Possible reason of alarm: heater 1 is overheat.
Integer PHOS.COOL.WDT.HEAT_COMP Alarm timeout: Block HEAT by COMP
This alarm blocks heater if compressors switched OFF during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: heater switch on when compressors is off. This operation mode forbidden.
Integer PHOS.COOL.WDT.PUMP_TPMIN Alarm timeout: Block PUMP by TPMIN
This alarm blocks pump (1,2) if pump cover temperature (T8,T9) less then threshold.
Negative timeout cause fatal Intelock.
Possible reason of alarm: pump frozen.
Integer PHOS.COOL.WDT.PUMP_TPMAX Alarm timeout: Block PUMP by TPMAX
This alarm blocks pump (1,2) if pump cover temperature (T8,T9) greater then threshold.
Negative timeout cause fatal Intelock.
Possible reason of alarm: pump overheat.
Integer PHOS.COOL.WDT.VE1_ADAMS Alarm timeout: Block VE1 by ADAMS
This alarm blocks freon vent Y1 if ADAM's errors coming during timeout.
Negative timeout cause fatal Intelock.
Possible reason of alarm: ADAM's failure or RS-485 network connection lost. ADAM's is RS-485 remote network data acquisition modules of I-7000 seria produced by ICP-DAS company.
Integer PHOS.COOL.WDT.PUMP_LLSLO Alarm timeout: Block PUMP by LLSLO
This alarm blocks pumps if cooling liquid (C6F14) level in receiver tank less then threshold during timeout, i.e. LLS.VL < LLS.LO.
Negative timeout cause fatal Intelock.
Possible reason of alarm: incufficient liquid level (leak), receiver tank is empty.
Integer PHOS.COOL.WDT.PUMP_LLSHI Alarm timeout: Block PUMP by LLSHI
This alarm blocks pumps if cooling liquid (C6F14) level in receiver tank greater then threshold during timeout, i.e. LLS.VL > LLS.HI.
Negative timeout cause fatal Intelock.
Possible reason of alarm: receiver tank is overfull.
Integer PHOS.COOL.WDT.COMP_TCMIN Alarm timeout: Block COMP by TCMIN
This alarm blocks compressor (to flow freon R404A) if compressor cover temperature (T11..T14) less then threshold during timeout, i.e. T11..T14 < Tcmin.
Negative timeout cause fatal Intelock.
Possible reason of alarm: compressor frozen.
Integer PHOS.COOL.WDT.COMP_TCMAX Alarm timeout: Block COMP by TCMAX
This alarm blocks compressor (to flow freon R404A) if compressor cover temperature (T11..T14) greater then threshold during timeout, i.e. T11..T14 > Tcmax.
Negative timeout cause fatal Intelock.
Possible reason of alarm: compressor overheat.
Integer PHOS.COOL.WDT.COMP_ECV Alarm timeout: Block COMP by ECV
This alarm blocks compressor (to flow freon R404A) if ECV controller raise alarm during timeout, i.e. ECV alarm flags is non-zero.
Negative timeout cause fatal Intelock.
Possible reason of alarm: ECV failure or network connection lost on LAN-2. Note that alidcscom252 cooling server uses LAN-1 for DIM connection, and LAN-2 - for ECV connection.
Integer PHOS.COOL.WDT.VE1_POWER Alarm timeout: Block VE1 by POWER
This alarm blocks VE1 (vent for freon R404A) if general power cut (380V) found during timeout, i.e. POWER flag is zero.
Negative timeout cause fatal Intelock.
Possible reason of alarm: general power cut.
Integer PHOS.COOL.WDT.VE1_WATER Alarm timeout: Block VE1 by WATER
This alarm blocks VE1 (vent for freon R404A) if water flow rate absence found during timeout, i.e. WATER flag is zero.
Negative timeout cause fatal Intelock.
Possible reason of alarm: general water failure.
Integer PHOS.FSM.FSM Enable/disable (1/0) PHOS cooling control thru FSM.
Integer PHOS.FSM.DIM Enable/disable (1/0) FSM control thru DIM.
Integer PHOS.FSM.STATE Finite State Machine state:
  1. OFF,
  2. STANDBY,
  3. CALIBRATION,
  4. COOLING,
  5. WARMING,
  6. READY,
  7. ERROR

FSM diagramm
Char PHOS.FSM.ACTION Command coming from PVSS level. Available next commands: SWITCH_OFF, GO_STANDBY, RESET, CALIBRATION, COOLING, WARMING, GO_READY. See picture above.
Double PHOS.COOL.PCPS.V1 Voltage, in Volts, of 1-st channel of fault protected PC Power Supply.
Double PHOS.COOL.PCPS.V2 Voltage, in Volts, of 2-nd channel of fault protected PC Power Supply.
Integer PHOS.COOL.PCPS.S1 Status (Voltage>15V) of 1-st channel of fault protected PC Power Supply.
Integer PHOS.COOL.PCPS.S2 Status (Voltage>15V) of 2-nd channel of fault protected PC Power Supply.
Double PHOS.MATR.PWOn.T_m PWOn temperature by Ni100 or Pt100 sensor m, n=0..5, m=0..23.
Integer PHOS.MATR.PWOn.WDT_m Watchdog status (0=fail,1=Ok) of PWOn temperature by Ni100 or Pt100 sensor m, n=0..5, m=0..23.
Double PHOS.MATR.FEEn.T_m FEEn temperature by Ni100 or Pt100 sensor m, n=0..5, m=0..7.
Double PHOS.MATR.FEEn.T2_m Temperature by humidity sensor m in module n, n=0..5, m=0..6. (H0,H2):FEE, (H1,H2,H3):PWO, (H4,H6):unused.
Double PHOS.MATR.FEEn.H_m Humidity (%) by humidity sensor m in module n, n=0..5, m=0..6. (H0,H2):FEE, (H1,H2,H3):PWO, (H4,H6):unused.
Integer PHOS.MATR.FEEn.WDT_m Watchdog status (0=fail,1=Ok) of sensor k, n=0..5, m=0..21.
m=0..7 corresponds to sensors PHOS.MATR.FEEn.T_k, k=m=0..7.
m=8..14 corresponds to sensors PHOS.MATR.FEEn.T2_k, k=m-8=0..6.
m=15..21 corresponds to sensors PHOS.MATR.FEEn.H_k, k=m-15=0..6.
Double PHOS.MATR.PWO1.T_0 PWO1 temperature by Pt100 sensor 0 - PTM16. ELMB7, Slot2, Pin29-32, R15.
Integer PHOS.MATR.PWO1.WDT_0 Watchdog for PHOS.MATR.PWO1.T_0

goto Content


List of public cooling DIM services

Service Name (Cmnd,Info) Content (list of tags)
ALICE/PHOS/COOLING/COOL/CLICK PHOS.COOL.CLICK
Command service for remote clients.
ALICE/PHOS/COOLING/COOL/NOTIFY PHOS.COOL.NOTIFY
ALICE/PHOS/COOLING/COOL/ALARM_LOG PHOS.COOL.ALARM_LOG
ALICE/PHOS/COOLING/COOL/CONSOLE PHOS.COOL.CONSOLE
Command service (Char) to setup control parameters.
Service should contanins command lines (CR,LF separated). Next commands available:
  • @AssignTag name=value - assign new value for tag with given name.
    For example:
    • Assign stabilization temperature in COOLING mode.
      @AssignTag PHOS.COOL.COOL.TSTAB=-25
    • Assign minimal number of compressors in COOLING mode.
      @AssignTag PHOS.COOL.COOL.NBMIN=2
    • Assign maximal number of compressors in COOLING mode.
      @AssignTag PHOS.COOL.COOL.NBMAX=4
  • @SaveParams - Save control parameters to INI file. That is uses to fix control parameters after all required parameters modified. Saved parameters can be restored by @LoadParams command. Saved parameters also will be applied on each system start.
  • @LoadParams - Load control parameters from INI file. That is uses to restore saved control parameters.
ALICE/PHOS/COOLING/COOL/HOST_TIME+HOST_INFO PHOS.COOL.HOST_TIME, PHOS.COOL.HOST_INFO
ALICE/PHOS/COOLING/COOL/DAQ/BUGS PHOS.COOL.DAQ.BUGS
ALICE/PHOS/COOLING/COOL/COM/BUGS PHOS.COOL.COM.BUGS
ALICE/PHOS/COOLING/COOL/P1 PHOS.COOL.P1
ALICE/PHOS/COOLING/COOL/P2 PHOS.COOL.P2
ALICE/PHOS/COOLING/COOL/P3 PHOS.COOL.P3
ALICE/PHOS/COOLING/COOL/T1 PHOS.COOL.T1
ALICE/PHOS/COOLING/COOL/T2 PHOS.COOL.T2
ALICE/PHOS/COOLING/COOL/T3 PHOS.COOL.T3
ALICE/PHOS/COOLING/COOL/T4 PHOS.COOL.T4
ALICE/PHOS/COOLING/COOL/T5 PHOS.COOL.T5
ALICE/PHOS/COOLING/COOL/T6 PHOS.COOL.T6
ALICE/PHOS/COOLING/COOL/T7 PHOS.COOL.T7
ALICE/PHOS/COOLING/COOL/T8 PHOS.COOL.T8
ALICE/PHOS/COOLING/COOL/T9 PHOS.COOL.T9
ALICE/PHOS/COOLING/COOL/T10 PHOS.COOL.T10
ALICE/PHOS/COOLING/COOL/T11 PHOS.COOL.T11
ALICE/PHOS/COOLING/COOL/T12 PHOS.COOL.T12
ALICE/PHOS/COOLING/COOL/T13 PHOS.COOL.T13
ALICE/PHOS/COOLING/COOL/T14 PHOS.COOL.T14
ALICE/PHOS/COOLING/COOL/T15 PHOS.COOL.T15
ALICE/PHOS/COOLING/COOL/T16 PHOS.COOL.T16
ALICE/PHOS/COOLING/COOL/T17 PHOS.COOL.T17
ALICE/PHOS/COOLING/COOL/T18 PHOS.COOL.T18
ALICE/PHOS/COOLING/COOL/T19 PHOS.COOL.T19
ALICE/PHOS/COOLING/COOL/T20 PHOS.COOL.T20
ALICE/PHOS/COOLING/COOL/T21 PHOS.COOL.T21
ALICE/PHOS/COOLING/COOL/T22 PHOS.COOL.T22
ALICE/PHOS/COOLING/
COOL/COMP1/ENB+POW+WTM+THR+OIL+LPR+HPR
PHOS.COOL.COMP1.ENB, PHOS.COOL.COMP1.POW, PHOS.COOL.COMP1.WTM, PHOS.COOL.COMP1.THR, PHOS.COOL.COMP1.OIL, PHOS.COOL.COMP1.LPR, PHOS.COOL.COMP1.HPR
ALICE/PHOS/COOLING/
COOL/COMP2/ENB+POW+WTM+THR+OIL+LPR+HPR
PHOS.COOL.COMP2.ENB, PHOS.COOL.COMP2.POW, PHOS.COOL.COMP2.WTM, PHOS.COOL.COMP2.THR, PHOS.COOL.COMP2.OIL, PHOS.COOL.COMP2.LPR, PHOS.COOL.COMP2.HPR
ALICE/PHOS/COOLING/
COOL/COMP3/ENB+POW+WTM+THR+OIL+LPR+HPR
PHOS.COOL.COMP3.ENB, PHOS.COOL.COMP3.POW, PHOS.COOL.COMP3.WTM, PHOS.COOL.COMP3.THR, PHOS.COOL.COMP3.OIL, PHOS.COOL.COMP3.LPR, PHOS.COOL.COMP3.HPR
ALICE/PHOS/COOLING/
COOL/COMP4/ENB+POW+WTM+THR+OIL+LPR+HPR
PHOS.COOL.COMP4.ENB, PHOS.COOL.COMP4.POW, PHOS.COOL.COMP4.WTM, PHOS.COOL.COMP4.THR, PHOS.COOL.COMP4.OIL, PHOS.COOL.COMP4.LPR, PHOS.COOL.COMP4.HPR
ALICE/PHOS/COOLING/
COOL/PUMP1/ENB+POW+WTM+THR
PHOS.COOL.PUMP1.ENB, PHOS.COOL.PUMP1.POW, PHOS.COOL.PUMP1.WTM, PHOS.COOL.PUMP1.THR
ALICE/PHOS/COOLING/
COOL/PUMP2/ENB+POW+WTM+THR
PHOS.COOL.PUMP2.ENB, PHOS.COOL.PUMP2.POW, PHOS.COOL.PUMP2.WTM, PHOS.COOL.PUMP2.THR
ALICE/PHOS/COOLING/COOL/FREON/ENB+VE1+LPR+HPR PHOS.COOL.FREON.ENB, PHOS.COOL.FREON.VE1, PHOS.COOL.FREON.LPR, PHOS.COOL.FREON.HPR
ALICE/PHOS/COOLING/COOL/FREON/ECV PHOS.COOL.FREON.ECV
ALICE/PHOS/COOLING/
COOL/LIQ/ENB+VE2+HLR+LLR+REED+TMIN+TMAX+
TSTAB+DELTA+NBSEN+DTMAX
PHOS.COOL.LIQ.ENB, PHOS.COOL.LIQ.VE2, PHOS.COOL.LIQ.HLR, PHOS.COOL.LIQ.LLR, PHOS.COOL.LIQ.REED, PHOS.COOL.LIQ.TMIN, PHOS.COOL.LIQ.TMAX, PHOS.COOL.LIQ.TSTAB, PHOS.COOL.LIQ.DELTA, PHOS.COOL.LIQ.NBSEN, PHOS.COOL.LIQ.DTMAX,
ALICE/PHOS/COOLING/COOL/LIQ/TSENS+TGOAL+TAVER PHOS.COOL.LIQ.TSENS, PHOS.COOL.LIQ.TGOAL, PHOS.COOL.LIQ.TAVER
ALICE/PHOS/COOLING/COOL/LIQ/CAVER+NAVER PHOS.COOL.LIQ.CAVER, PHOS.COOL.LIQ.NAVER
ALICE/PHOS/COOLING/COOL/LIQ/NCOMP PHOS.COOL.LIQ.NCOMP
ALICE/PHOS/COOLING/COOL/LIQ/NFDBK+TFDBK PHOS.COOL.LIQ.NFDBK, PHOS.COOL.LIQ.TFDBK
ALICE/PHOS/COOLING/COOL/LIQ/LLS/MM+PC+VL PHOS.COOL.LIQ.LLS.MM, PHOS.COOL.LIQ.LLS.PC, PHOS.COOL.LIQ.LLS.VL
ALICE/PHOS/COOLING/
COOL/LIQ/LLS/LO+HI
PHOS.COOL.LIQ.LLS.LO, PHOS.COOL.LIQ.LLS.HI
ALICE/PHOS/COOLING/COOL/FAN/ENB+POW+WTM+TON PHOS.COOL.FAN.ENB, PHOS.COOL.FAN.POW, PHOS.COOL.FAN.WTM, PHOS.COOL.FAN.TON
ALICE/PHOS/COOLING/COOL/FAN1/ENB+POW PHOS.COOL.FAN1.ENB, PHOS.COOL.FAN1.POW
ALICE/PHOS/COOLING/COOL/FAN2/ENB+POW PHOS.COOL.FAN2.ENB, PHOS.COOL.FAN2.POW
ALICE/PHOS/COOLING/COOL/FAN3/ENB+POW PHOS.COOL.FAN3.ENB, PHOS.COOL.FAN3.POW
ALICE/PHOS/COOLING/COOL/FAN4/ENB+POW PHOS.COOL.FAN4.ENB, PHOS.COOL.FAN4.POW
ALICE/PHOS/COOLING/
COOL/HEAT1/ENB+POW+SSR+PER+Q+QMAX
PHOS.COOL.HEAT1.ENB, PHOS.COOL.HEAT1.POW, PHOS.COOL.HEAT1.SSR, PHOS.COOL.HEAT1.PER, PHOS.COOL.HEAT1.Q, PHOS.COOL.HEAT1.QMAX
ALICE/PHOS/COOLING/
COOL/HEAT2/ENB+POW+SSR+PER+Q+QMAX
PHOS.COOL.HEAT2.ENB, PHOS.COOL.HEAT2.POW, PHOS.COOL.HEAT2.SSR, PHOS.COOL.HEAT2.PER, PHOS.COOL.HEAT2.Q, PHOS.COOL.HEAT2.QMAX
ALICE/PHOS/COOLING/
COOL/HEAT3/ENB+POW+SSR+PER+Q+QMAX
PHOS.COOL.HEAT3.ENB, PHOS.COOL.HEAT3.POW, PHOS.COOL.HEAT3.SSR, PHOS.COOL.HEAT3.PER, PHOS.COOL.HEAT3.Q, PHOS.COOL.HEAT3.QMAX
ALICE/PHOS/COOLING/
COOL/COMP/P1MIN+P1MAX+P2MIN+P2MAX+
NBMIN+NBMAX+POLLTM+DEADTM
PHOS.COOL.COMP.P1MIN, PHOS.COOL.COMP.P1MAX, PHOS.COOL.COMP.P2MIN, PHOS.COOL.COMP.P2MAX, PHOS.COOL.COMP.NBMIN, PHOS.COOL.COMP.NBMAX, PHOS.COOL.COMP.POLLTM, PHOS.COOL.COMP.DEADTM
ALICE/PHOS/COOLING/COOL/COMP/TCMIN+TCMAX+CYCLE PHOS.COOL.COMP.TCMIN, PHOS.COOL.COMP.TCMAX, PHOS.COOL.COMP.CYCLE
ALICE/PHOS/COOLING/
COOL/PUMP/P3MIN+P3MAX+TPMIN+TPMAX+CYCLE
PHOS.COOL.PUMP.P3MIN, PHOS.COOL.PUMP.P3MAX, PHOS.COOL.PUMP.TPMIN, PHOS.COOL.PUMP.TPMAX, PHOS.COOL.PUMP.CYCLE
ALICE/PHOS/COOLING/COOL/HEATS/T4MAX PHOS.COOL.HEATS.T4MAX
ALICE/PHOS/COOLING/COOL/INTERLOCK PHOS.COOL.INTERLOCK
ALICE/PHOS/COOLING/COOL/CMD/CTRL PHOS.COOL.CMD.CTRL
ALICE/PHOS/COOLING/COOL/CMD/BLK PHOS.COOL.CMD.BLK
ALICE/PHOS/COOLING/COOL/BLK/NUM PHOS.COOL.BLK.NUM
ALICE/PHOS/COOLING/COOL/BLK/OPT1+OPT2 PHOS.COOL.BLK.OPT1, PHOS.COOL.BLK.OPT2
ALICE/PHOS/COOLING/
STBY/TSTAB+DELTA+NBMIN+NBMAX+POLLTM+DEADTM+
NBSEN+DTMAX+Q1+Q2+Q3
PHOS.COOL.STBY.TSTAB, PHOS.COOL.STBY.DELTA, PHOS.COOL.STBY.NBMIN, PHOS.COOL.STBY.NBMAX, PHOS.COOL.STBY.POLLTM, PHOS.COOL.STBY.DEADTM, PHOS.COOL.STBY.NBSEN, PHOS.COOL.STBY.DTMAX, PHOS.COOL.STBY.Q1, PHOS.COOL.STBY.Q2, PHOS.COOL.STBY.Q3
ALICE/PHOS/COOLING/
COOL/TSTAB+DELTA+NBMIN+NBMAX+POLLTM+DEADTM+
NBSEN+DTMAX+Q1+Q2+Q3
PHOS.COOL.COOL.TSTAB, PHOS.COOL.COOL.DELTA, PHOS.COOL.COOL.NBMIN, PHOS.COOL.COOL.NBMAX, PHOS.COOL.COOL.POLLTM, PHOS.COOL.COOL.DEADTM, PHOS.COOL.COOL.NBSEN, PHOS.COOL.COOL.DTMAX, PHOS.COOL.COOL.Q1, PHOS.COOL.COOL.Q2, PHOS.COOL.COOL.Q3
ALICE/PHOS/COOLING/
WARM/TSTAB+DELTA+NBMIN+NBMAX+POLLTM+DEADTM+
NBSEN+DTMAX+Q1+Q2+Q3
PHOS.COOL.WARM.TSTAB, PHOS.COOL.WARM.DELTA, PHOS.COOL.WARM.NBMIN, PHOS.COOL.WARM.NBMAX, PHOS.COOL.WARM.POLLTM, PHOS.COOL.WARM.DEADTM, PHOS.COOL.WARM.NBSEN, PHOS.COOL.WARM.DTMAX, PHOS.COOL.WARM.Q1, PHOS.COOL.WARM.Q2, PHOS.COOL.WARM.Q3
ALICE/PHOS/COOLING/
COOL/ECV/DISPLAY/NVOMO01-18
PHOS.COOL.ECV.nvomo01, PHOS.COOL.ECV.nvomo02, PHOS.COOL.ECV.nvomo03, PHOS.COOL.ECV.nvomo04, PHOS.COOL.ECV.nvomo05, PHOS.COOL.ECV.nvomo06, PHOS.COOL.ECV.nvomo07, PHOS.COOL.ECV.nvomo08, PHOS.COOL.ECV.nvomo09, PHOS.COOL.ECV.nvomo10, PHOS.COOL.ECV.nvomo11, PHOS.COOL.ECV.nvomo12, PHOS.COOL.ECV.nvomo13, PHOS.COOL.ECV.nvomo14, PHOS.COOL.ECV.nvomo15, PHOS.COOL.ECV.nvomo16, PHOS.COOL.ECV.nvomo17, PHOS.COOL.ECV.nvomo18
ALICE/PHOS/COOLING/
COOL/WDT/VE1_LPR+VE1_HPR+PUMP_THR+PUMP_VE2+
PUMP_LLR+PUMP_HLR+PUMP_P3MIN+PUMP_P3MAX+
PUMP_TMIN+PUMP_TMAX
PHOS.COOL.WDT.VE1_LPR, PHOS.COOL.WDT.VE1_HPR, PHOS.COOL.WDT.PUMP_THR, PHOS.COOL.WDT.PUMP_VE2, PHOS.COOL.WDT.PUMP_LLR, PHOS.COOL.WDT.PUMP_HLR, PHOS.COOL.WDT.PUMP_P3MIN, PHOS.COOL.WDT.PUMP_P3MAX, PHOS.COOL.WDT.PUMP_TMIN, PHOS.COOL.WDT.PUMP_TMAX
ALICE/PHOS/COOLING/
COOL/WDT/COMP_THR+COMP_OIL+
COMP_LPR+COMP_HPR+COMP_P1MIN+COMP_P1MAX+
COMP_P2MIN+COMP_P2MAX+
COMP_VE1+COMP_PUMP
PHOS.COOL.WDT.COMP_THR, PHOS.COOL.WDT.COMP_OIL, PHOS.COOL.WDT.COMP_LPR, PHOS.COOL.WDT.COMP_HPR, PHOS.COOL.WDT.COMP_P1MIN, PHOS.COOL.WDT.COMP_P1MAX, PHOS.COOL.WDT.COMP_P2MIN, PHOS.COOL.WDT.COMP_P2MAX, PHOS.COOL.WDT.COMP_VE1, PHOS.COOL.WDT.COMP_PUMP
ALICE/PHOS/COOLING/
COOL/WDT/HEAT_VE2+HEAT_PUMP+
HEAT_T4MAX+HEAT_COMP+PUMP_TPMIN+PUMP_TPMAX+
VE1_ADAMS+PUMP_LLSLO+PUMP_LLSHI
PHOS.COOL.WDT.HEAT_VE2, PHOS.COOL.WDT.HEAT_PUMP, PHOS.COOL.WDT.HEAT_T4MAX, PHOS.COOL.WDT.HEAT_COMP, PHOS.COOL.WDT.PUMP_TPMIN, PHOS.COOL.WDT.PUMP_TPMAX, PHOS.COOL.WDT.VE1_ADAMS, PHOS.COOL.WDT.PUMP_LLSLO, PHOS.COOL.WDT.PUMP_LLSHI
ALICE/PHOS/COOLING/
COOL/WDT/COMP_TCMIN+COMP_TCMAX+COMP_ECV
PHOS.COOL.WDT.COMP_TCMIN, PHOS.COOL.WDT.COMP_TCMAX, PHOS.COOL.WDT.COMP_ECV
ALICE/PHOS/COOLING/
COOL/FREON/POWER+WATER
PHOS.COOL.FREON.POWER, PHOS.COOL.FREON.WATER
ALICE/PHOS/COOLING/
COOL/WDT/VE1_POWER+VE1_WATER
PHOS.COOL.WDT.VE1_POWER, PHOS.COOL.WDT.VE1_WATER
ALICE/PHOS/COOLING/
COOL/WATER/FLOW
PHOS.COOL.WATER.FLOW
ALICE/PHOS/COOLING/
COOL/WATER/FEDGE+PEDGE
PHOS.COOL.WATER.FEDGE, PHOS.COOL.WATER.PEDGE
ALICE/PHOS/COOLING/
COOL/PCPS/V1+V2+S1+S2
PHOS.COOL.PCPS.V1, PHOS.COOL.PCPS.V2, PHOS.COOL.PCPS.S1, PHOS.COOL.PCPS.S2.
, ,
, ,

goto Content