This document describe public tags and DIM services of the cooling system.
Content |
|
| Type | Name of tag | Comment information |
| Char[] | PHOS.COOL.CLICK | Remote click information (for remote clients). |
| Char[] | PHOS.COOL.NOTIFY | Remote click notification (for remote clients). |
| Char[] | PHOS.COOL.ALARM_LOG | Message on alarm (Interlock).
It contains semicolon-separated lines which exlain reason of Interlock if one happened.
This message is also to be saved into PHOS_DATA\ALARM.LOG log-file.
For example:
INTERLOCK FROM ALIDCSCOM252;TIME: 2009.10.20-10:08:04;REASON: PUMP1 by TPMAX.;ACTION: COOLING SYSTEM HALTED FOR SAFETY;; |
| Char[] | PHOS.COOL.CONSOLE | Console for incoming commands. |
| Double | PHOS.COOL.HOST_TIME | Server (alidcscom252) time, milliseconds since Xmas (01.01.01-00:00:00). Updates each second. |
| Char[] | PHOS.COOL.HOST_INFO | Server (alidcscom252) date-time pid@hostname, like 2009.10.11-15:30:00 346@ALIDCSCOM252. Updates each second. |
| Double | PHOS.COOL.P1 | Pressure sensor in Condensing tube, Bar (absolute). |
| Double | PHOS.COOL.P2 | Pressure sensor in Evaporating (suction) tube, Bar (absolute). |
| Double | PHOS.COOL.P3 | Pressure sensor in cooling liquid (C6F14) pipe, Bar (absolute). |
| Double | PHOS.COOL.T1 | Temperature of cooling liguid (C6F14) output (penal in small tank), °C. Pt-100 RTD sensor PTB_05. That is main feedback parameter to control liquid temperature. |
| Double | PHOS.COOL.T2 | Temperature of cooling liguid (C6F14) output (penal in small tank), °C. Pt-100 RTD sensor PTB_06. That is reserved feedback parameter to control liquid temperature. |
| Double | PHOS.COOL.T3 | Temperature of cooling liquid (C6F14) in Receiver (big tank), °C. |
| Double | PHOS.COOL.T4 | Temperature of Heater 1, °C. Pt-100 RTD sensor PTS_10. |
| Double | PHOS.COOL.T5 | Temperature of Air inside cooling machine cover, °C. PTC sensor CARNO_T5. |
| Double | PHOS.COOL.T6 | Temperature of Control unit inside cooling machine, °C. ADAM4 cold junction. |
| Double | PHOS.COOL.T7 | Temperature of freon evaporating, °C. Calculated by P2 via R404A table. |
| Double | PHOS.COOL.T8 | Temperature of Pump1 cover, °C. Pt-100 RTD sensor PTS_42. |
| Double | PHOS.COOL.T9 | Temperature of Pump2 cover, °C. Pt-100 RTD sensor PTS_03. |
| Double | PHOS.COOL.T10 | Temperature of Air inside pump station cover, °C. ADAM6 cold junction. |
| Double | PHOS.COOL.T11 | Temperature °C of compressor 1 cover, °C. Pt-100 RTD sensor PTS_20. |
| Double | PHOS.COOL.T12 | Temperature °C of compressor 2 cover, °C. Ni-100 RTD sensor 0070. |
| Double | PHOS.COOL.T13 | Temperature °C of compressor 3 cover, °C. Ni-100 RTD sensor 0063. |
| Double | PHOS.COOL.T14 | Temperature °C of compressor 4 cover, °C. Ni-100 RTD sensor 0045. |
| Double | PHOS.COOL.T15 | Temperature °C of PHOS input pipeline. Pt-100 RTD sensor PTS_06. |
| Double | PHOS.COOL.T16 | Temperature °C of PHOS output pipeline. Pt-100 RTD sensor PTS_09. |
| Double | PHOS.COOL.T17 | Temperature of freon condensing, °C. Calculated by P1 via R404A table. |
| Double | PHOS.COOL.T18 | Temperature output-input difference, °C. Calculated as T16-T15. |
| Double | PHOS.COOL.T19 | Temperature output-input difference, °C. Calculated as T3-T1. |
| Double | PHOS.COOL.T20 | Temperature of pump ¹2 motor cover, °C. |
| Double | PHOS.COOL.T21 | Temperature of pump ¹1 motor cover, °C. |
| Double | PHOS.COOL.T22 | Temperature difference, °C, of cradle output - input, by sensors PWO3.T_10 - PWO3.T_11. |
| Integer | PHOS.COOL.COMP1.ENB | Compressor ¹ 1 enable/disable (1/0). |
| Integer | PHOS.COOL.COMP1.POW | Compressor ¹ 1 power on/off (1/0). |
| Double | PHOS.COOL.COMP1.WTM | Compressor ¹ 1 working time (summary). Compressors works in round-robin order to equalize working times. |
| Integer | PHOS.COOL.COMP1.THR | Compressor ¹ 1 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm. |
| Integer | PHOS.COOL.COMP1.OIL | Compressor ¹ 1 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm. |
| Integer | PHOS.COOL.COMP1.LPR | Compressor ¹ 1 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure. |
| Integer | PHOS.COOL.COMP1.HPR | Compressor ¹ 1 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure. |
| Integer | PHOS.COOL.COMP2.ENB | Compressor ¹ 2 enable/disable (1/0). |
| Integer | PHOS.COOL.COMP2.POW | Compressor ¹ 2 power on/off (1/0). |
| Double | PHOS.COOL.COMP2.WTM | Compressor ¹ 2 working time (summary). Compressors works in round-robin order to equalize working times. |
| Integer | PHOS.COOL.COMP2.THR | Compressor ¹ 2 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm. |
| Integer | PHOS.COOL.COMP2.OIL | Compressor ¹ 2 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm. |
| Integer | PHOS.COOL.COMP2.LPR | Compressor ¹ 2 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure. |
| Integer | PHOS.COOL.COMP2.HPR | Compressor ¹ 2 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure. |
| Integer | PHOS.COOL.COMP3.ENB | Compressor ¹ 3 enable/disable (1/0). |
| Integer | PHOS.COOL.COMP3.POW | Compressor ¹ 3 power on/off (1/0). |
| Double | PHOS.COOL.COMP3.WTM | Compressor ¹ 3 working time (summary). Compressors works in round-robin order to equalize working times. |
| Integer | PHOS.COOL.COMP3.THR | Compressor ¹ 3 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm. |
| Integer | PHOS.COOL.COMP3.OIL | Compressor ¹ 3 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm. |
| Integer | PHOS.COOL.COMP3.LPR | Compressor ¹ 3 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure. |
| Integer | PHOS.COOL.COMP3.HPR | Compressor ¹ 3 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure. |
| Integer | PHOS.COOL.COMP4.ENB | Compressor ¹ 4 enable/disable (1/0). |
| Integer | PHOS.COOL.COMP4.POW | Compressor ¹ 4 power on/off (1/0). |
| Double | PHOS.COOL.COMP4.WTM | Compressor ¹ 4 working time (summary). Compressors works in round-robin order to equalize working times. |
| Integer | PHOS.COOL.COMP4.THR | Compressor ¹ 4 thermo relay on/off (1/0). Thermo relay on means compressor overload and may cause alarm. |
| Integer | PHOS.COOL.COMP4.OIL | Compressor ¹ 4 oil low level relay on/off (1/0). This singnal means lack of oil and may cause alarm. |
| Integer | PHOS.COOL.COMP4.LPR | Compressor ¹ 4 low pressure relay on/off (1/0). This signal means lack of freon and may cause alarm. Possible reason - freon leak or ECV failure. |
| Integer | PHOS.COOL.COMP4.HPR | Compressor ¹ 4 high pressure relay on/off (1/0). This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure. |
| Integer | PHOS.COOL.PUMP1.ENB | Pump ¹ 1 enable/disable (1/0). Disabled pump can't be powered on. |
| Integer | PHOS.COOL.PUMP1.POW | Pump ¹ 1 power on/off (1/0). |
| Double | PHOS.COOL.PUMP1.WTM | Pump ¹ 1 working time (summary). Pumps works in round-robin order to equalize working times. |
| Integer | PHOS.COOL.PUMP1.THR | Pump ¹ 1 thermo relay on/off (1/0). This signal means pump overload and may cause alarm. |
| Integer | PHOS.COOL.PUMP2.ENB | Pump ¹ 2 enable/disable (1/0). Disabled pump can't be powered on. |
| Integer | PHOS.COOL.PUMP2.POW | Pump ¹ 2 power on/off (1/0). |
| Double | PHOS.COOL.PUMP2.WTM | Pump ¹ 2 working time (summary). Pumps works in round-robin order to equalize working times. |
| Integer | PHOS.COOL.PUMP2.THR | Pump ¹ 2 thermo relay on/off (1/0). This signal means pump overload and may cause alarm. |
| Integer | PHOS.COOL.FREON.ENB | Freon (R404A) vent Y1 enable/disable (1/0). Disabled vent can't be powered on. |
| Integer | PHOS.COOL.FREON.VE1 | Freon (R404A) solenoid vent power on/off (1/0). Vent opening enables freon flow. |
| Integer | PHOS.COOL.FREON.LPR | Low freon (R404A) pressure relay on/off. This signal means lack of freon and may cause alarm. Possible reason - freon leak. |
| Integer | PHOS.COOL.FREON.HPR | High freon (R404A) pressure relay. This signal means freon overpressure and may cause alarm. Possible reason - water cooling failure. |
| Integer | PHOS.COOL.FREON.ECV | ECV state. 0 means Ok. Otherwise Bit0=NotOk, Bit1=Alarm, Bit2=TimeOut. ECV is Electrical Control Valve with Emerson controller EC3-X32 to control freon (R404A) flow. |
| Integer | PHOS.COOL.FREON.POWER | Indicate presence of genegal power (380V) for cooling machine (1=ON,0=OFF). |
| Integer | PHOS.COOL.FREON.WATER | Indicate presence of water cooling (1=ON,0=OFF). Calculated like that: if((PHOS.COOL.WATER.FLOW≥PHOS.COOL.WATER.FEDGE) or (PHOS.COOL.P1<PHOS.COOL.WATER.PEDGE)) then PHOS.COOL.FREON.WATER:=1 else PHOS.COOL.FREON.WATER:=0. |
| Double | PHOS.COOL.WATER.FLOW | Indicate water flow rate, Liters per minute. |
| Double | PHOS.COOL.WATER.FEDGE | Threshold for water flow rate to detect WATER, see PHOS.COOL.FREON.WATER. |
| Double | PHOS.COOL.WATER.PEDGE | Threshold for P1 to detect WATER, see PHOS.COOL.FREON.WATER. |
| Integer | PHOS.COOL.LIQ.ENB | Cooling liquid (C6F14) vent Y2 enable/disable (1/0). Disabled vent could not be powered on. |
| Integer | PHOS.COOL.LIQ.VE2 | Cooling liquid (C6F14) solenoid vent Y1 power on/off (1/0). |
| Integer | PHOS.COOL.LIQ.HLR | Cooling liquid (C6F14) high level relay on/off (1/0). This signal means liquid overpressure and may cause alarm. Possible reason - thrombus in pipes. |
| Integer | PHOS.COOL.LIQ.LLR | Cooling liquid (C6F14) low level relay on/off (1/0). This signal means lack of liquid and may cause alarm. Possible reason - liquid leak. |
| Integer | PHOS.COOL.LIQ.REED | 4-bit state of 4 reed switches of liquid level. Bit 0 means empty receiver tank, bit 3 - full tank. |
| Double | PHOS.COOL.LIQ.TMIN | Cooling liquid (C6F14) temperature low level,°C. Uses to generate alarm on cooling liquid temperature. |
| Double | PHOS.COOL.LIQ.TMAX | Cooling liquid (C6F14) temperature high level,°C. Uses to generate alarm on cooling liquid temperature. |
| Double | PHOS.COOL.LIQ.TSTAB | Cooling liquid (C6F14) nominal ("wanted") stabilization temperature,°C. Note that actual ("applied") stabilization temperature PHOS.COOL.LIQ.TGOAL also depends on PHOS.COOL.LIQ.DTMAX and current PWO temperature PHOS.COOL.LIQ.TSENS (to avoid PWO damage due to temperature gradient). |
| Double | PHOS.COOL.LIQ.DELTA | Cooling liquid (C6F14) temperature stabilization corridor,°C. Compressor(s) turn on/off temperature = TGOAL ± DELTA. |
| Integer | PHOS.COOL.LIQ.NBSEN | This tag define which sensor (i.e. PHOS module number in 0..4 range) uses for control cooling speed. This sensor uses to calculate PHOS.COOL.LIQ.TSENS. |
| Double | PHOS.COOL.LIQ.DTMAX | Maximal temperature difference for cooling speed control,°C. Uses to calculate "applied" stabilization temperature PHOS.COOL.LIQ.TGOAL. |
| Double | PHOS.COOL.LIQ.TSENS | Current PWO sensor (by PHOS.COOL.LIQ.NBSEN) temperature,°C. Uses to calculate "applied" stabilization temperature PHOS.COOL.LIQ.TGOAL. |
| Double | PHOS.COOL.LIQ.TGOAL | Current actual ("applied") cooling liquid (C6F14) stabilization ("goal") temperature,°C. Compressor(s) turn on/off temperature = TGOAL ± DELTA. TGOAL calculates by TSTAB with condition ABS(TSENS-TGOAL)<=DTMAX. If ABS(TSENS-TSTAB)<=DTMAX or DTMAX=0, then TGOAL=DTMAX. Otherwise TGOAL=MIN(TSENS+DTMAX,MAX(TSENS-DTMAX,TSTAB)). This condition guarantee limited temperature gradient to avoid PWO damage. |
| Double | PHOS.COOL.LIQ.TAVER | Current cooling liquid (C6F14) average (over control cycle) temperature,°C.![]() |
| Double | PHOS.COOL.LIQ.CAVER | Current average control cycle period, minutes (see picture above). |
| Double | PHOS.COOL.LIQ.NAVER | Current average number of working compressors per cycle. It's proportional to average cooling power per cycle. |
| Integer | PHOS.COOL.LIQ.NCOMP | Current number of working compressors (0..4). |
| Double | PHOS.COOL.LIQ.LLS.MM | Current cooling liquid (C6F14) level in receiver tank, mm. |
| Double | PHOS.COOL.LIQ.LLS.PC | Current cooling liquid (C6F14) level in receiver tank, % of tank volume (65L). |
| Double | PHOS.COOL.LIQ.LLS.VL | Current cooling liquid (C6F14) level in receiver tank, liters. |
| Double | PHOS.COOL.LIQ.LLS.LO | Low cooling liquid (C6F14) level threshold for alarm, Liters. |
| Double | PHOS.COOL.LIQ.LLS.HI | High cooling liquid (C6F14) level threshold for alarm, Liters. |
| Integer | PHOS.COOL.LIQ.NFDBK | Number of feedback sensor, 1=T1, 2=T2, 3=T1 and T2. This number define, which sensor uses to calculate feedback temperature for stabilization. |
| Double | PHOS.COOL.LIQ.TFDBK | Temperature of feedback sensor, T1 or T2 or (T1+T2)/2. |
| Integer | PHOS.COOL.FAN.ENB | Fan enable/disable (1/0). Disabled fan can't be powered on. |
| Integer | PHOS.COOL.FAN.POW | Fan power on/off (1/0). |
| Double | PHOS.COOL.FAN.WTM | Fan working time (summary), hours. |
| Double | PHOS.COOL.FAN.TON | Fan turn on temperature, °C. |
| Integer | PHOS.COOL.FAN1.ENB | Fan1 (pump 1 inflow and outflow) enable/disable (1/0). Disabled fan can't be powered on. |
| Integer | PHOS.COOL.FAN1.POW | Fan1 (pump 1 inflow and outflow) power on/off (1/0). |
| Integer | PHOS.COOL.FAN2.ENB | Fan2 (pump 2 inflow and outflow) enable/disable (1/0). Disabled fan can't be powered on. |
| Integer | PHOS.COOL.FAN2.POW | Fan2 (pump 2 inflow and outflow) power on/off (1/0). |
| Integer | PHOS.COOL.FAN3.ENB | Fan3 (compressor station outflow) enable/disable (1/0). Disabled fan can't be powered on. |
| Integer | PHOS.COOL.FAN3.POW | Fan3 (compressor station outflow) power on/off (1/0). |
| Integer | PHOS.COOL.FAN4.ENB | Fan4 (compressor station inflow) enable/disable (1/0). Disabled fan can't be powered on. |
| Integer | PHOS.COOL.FAN4.POW | Fan4 (compressor station inflow) power on/off (1/0). |
| Integer | PHOS.COOL.HEAT1.ENB | Heat ¹ 1 enable/disable (1/0). |
| Integer | PHOS.COOL.HEAT1.POW | Heat ¹ 1 power on/off (1/0). |
| Integer | PHOS.COOL.HEAT1.SSR | Heat ¹ 1 solid state relay on/off (1/0). |
| Integer | PHOS.COOL.HEAT1.PER | Heat ¹ 1 period, ms. |
| Double | PHOS.COOL.HEAT1.Q | Heat ¹ 1 power, %. 100% correspond to 1 kW. T4 uses to control heater temperature |
| Double | PHOS.COOL.HEAT1.QMAX | Heat ¹ 1 maximal power, %. |
| Integer | PHOS.COOL.HEAT2.ENB | Heat ¹ 2 enable/disable (1/0). |
| Integer | PHOS.COOL.HEAT2.POW | Heat ¹ 2 power on/off (1/0). |
| Integer | PHOS.COOL.HEAT2.SSR | Heat ¹ 2 solid state relay on/off (1/0). |
| Integer | PHOS.COOL.HEAT2.PER | Heat ¹ 2 period, ms. |
| Double | PHOS.COOL.HEAT2.Q | Heat ¹ 2 power, %. |
| Double | PHOS.COOL.HEAT2.QMAX | Heat ¹ 2 maximal power, %. |
| Integer | PHOS.COOL.HEAT3.ENB | Heat ¹ 3 enable/disable (1/0). |
| Integer | PHOS.COOL.HEAT3.POW | Heat ¹ 3 power on/off (1/0). |
| Integer | PHOS.COOL.HEAT3.SSR | Heat ¹ 3 solid state relay on/off (1/0). |
| Integer | PHOS.COOL.HEAT3.PER | Heat ¹ 3 period, ms. |
| Double | PHOS.COOL.HEAT3.Q | Heat ¹ 3 power, %. |
| Double | PHOS.COOL.HEAT3.QMAX | Heat ¹ 3 maximal power, %. |
| Double | PHOS.COOL.COMP.P1MIN | Minimal condensator pressure, Bar. Threshold for alarms. |
| Double | PHOS.COOL.COMP.P1MAX | Maximal condensator pressure, Bar. Threshold for alarms. |
| Double | PHOS.COOL.COMP.P2MIN | Minimal evaporating pressure, Bar. Threshold for alarms. |
| Double | PHOS.COOL.COMP.P2MAX | Maximal evaporating pressure, Bar. Threshold for alarms. |
| Integer | PHOS.COOL.COMP.NBMIN | Minimal number of working compressors. |
| Integer | PHOS.COOL.COMP.NBMAX | Maximal number of working compressors. |
| Double | PHOS.COOL.COMP.POLLTM | Polling period, seconds. |
| Double | PHOS.COOL.COMP.DEADTM | Dead time after on/off, seconds. |
| Double | PHOS.COOL.COMP.TCMIN | Minimal compressor cover temperature,°C. Threshold for alarms. |
| Double | PHOS.COOL.COMP.TCMAX | Maximal compressor cover temperature,°C. Threshold for alarms. |
| Double | PHOS.COOL.COMP.CYCLE | Compressor shift cycle, hours. |
| Double | PHOS.COOL.PUMP.P3MIN | Minimal pressure liquid limit, Bar. Threshold for alarms. |
| Double | PHOS.COOL.PUMP.P3MAX | Maximal pressure liquid limit, Bar. Threshold for alarms. |
| Double | PHOS.COOL.PUMP.TPMIN | Minimal pump body (cover) temperature, °C. Threshold for alarms. |
| Double | PHOS.COOL.PUMP.TPMAX | Maximal pump body (cover) temperature, °C. Threshold for alarms. |
| Double | PHOS.COOL.PUMP.CYCLE | Pump shift cycle, hours. |
| Double | PHOS.COOL.HEATS.T4MAX | High T4 heater ¹1 limit, °C. Threshold for alarms. |
| Double | PHOS.COOL.STBY.TSTAB | Liquid stabilization temperature (for STANDBY state), °C. This parameter copied to PHOS.COOL.LIQ.TSTAB when system going to STANDBY state. |
| Double | PHOS.COOL.STBY.DELTA | Temperature corridor (for STANDBY state). Compressor turn on/off temperature = TSTAB ± DELTA. This parameter copied to PHOS.COOL.LIQ.DELTA when system going to STANDBY state. |
| Integer | PHOS.COOL.STBY.NBMIN | Minimal number of working compressors (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.NBMIN when system going to STANDBY state. |
| Integer | PHOS.COOL.STBY.NBMAX | Maximal number of working compressors (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.NBMAX when system going to STANDBY state. |
| Double | PHOS.COOL.STBY.POLLTM | Polling period, seconds (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.POLLTM when system going to STANDBY state. |
| Double | PHOS.COOL.STBY.DEADTM | Dead time after on/off, seconds (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.DEADTM when system going to STANDBY state. |
| Integer | PHOS.COOL.STBY.NBSEN | Sensor number for cooling speed control (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.NBSEN when system going to STANDBY state. |
| Double | PHOS.COOL.STBY.DTMAX | Maximal temperature delta for cooling speed control,°C (for STANDBY state). This parameter copied to PHOS.COOL.LIQ.DTMAX when system going to STANDBY state. |
| Double | PHOS.COOL.STBY.Q1 | Heat ¹1 power, % (for STANDBY state). This parameter copied to PHOS.COOL.HEAT1.Q when system going to STANDBY state. |
| Double | PHOS.COOL.STBY.Q2 | Heat ¹2 power, % (for STANDBY state). This parameter copied to PHOS.COOL.HEAT2.Q when system going to STANDBY state. |
| Double | PHOS.COOL.STBY.Q3 | Heat ¹3 power, % (for STANDBY state). This parameter copied to PHOS.COOL.HEAT3.Q when system going to STANDBY state. |
| Double | PHOS.COOL.COOL.TSTAB | Liquid stabilization temperature (for COOLING state), °C. This parameter copied to PHOS.COOL.LIQ.TSTAB when system going to COOLING state. |
| Double | PHOS.COOL.COOL.DELTA | Temperature corridor (for COOLING state). Compressor turn on/off temperature = TSTAB ± DELTA. This parameter copied to PHOS.COOL.LIQ.DELTA when system going to COOLING state. |
| Integer | PHOS.COOL.COOL.NBMIN | Minimal number of working compressors (for COOLING state). This parameter copied to PHOS.COOL.LIQ.NBMIN when system going to COOLING state. |
| Integer | PHOS.COOL.COOL.NBMAX | Maximal number of working compressors (for COOLING state). This parameter copied to PHOS.COOL.LIQ.NBMAX when system going to COOLING state. |
| Double | PHOS.COOL.COOL.POLLTM | Polling period, seconds (for COOLING state). This parameter copied to PHOS.COOL.LIQ.POLLTM when system going to COOLING state. |
| Double | PHOS.COOL.COOL.DEADTM | Dead time after on/off, seconds (for COOLING state). This parameter copied to PHOS.COOL.LIQ.DEADTM when system going to COOLING state. |
| Integer | PHOS.COOL.COOL.NBSEN | Sensor number for cooling speed control (for COOLING state). This parameter copied to PHOS.COOL.LIQ.NBSEN when system going to COOLING state. |
| Double | PHOS.COOL.COOL.DTMAX | Maximal temperature delta for cooling speed control,°C (for COOLING state). This parameter copied to PHOS.COOL.LIQ.DTMAX when system going to COOLING state. |
| Double | PHOS.COOL.COOL.Q1 | Heat ¹1 power, % (for COOLING state). This parameter copied to PHOS.COOL.HEAT1.Q when system going to COOLING state. |
| Double | PHOS.COOL.COOL.Q2 | Heat ¹2 power, % (for COOLING state). This parameter copied to PHOS.COOL.HEAT2.Q when system going to COOLING state. |
| Double | PHOS.COOL.COOL.Q3 | Heat ¹3 power, % (for COOLING state). This parameter copied to PHOS.COOL.HEAT3.Q when system going to COOLING state. |
| Double | PHOS.COOL.WARM.TSTAB | Liquid stabilization temperature (for WARMING state), °C. This parameter copied to PHOS.COOL.LIQ.TSTAB when system going to WARMING state. |
| Double | PHOS.COOL.WARM.DELTA | Temperature corridor (for WARMING state). Compressor turn on/off temperature = TSTAB ± DELTA. This parameter copied to PHOS.COOL.LIQ.DELTA when system going to WARMING state. |
| Integer | PHOS.COOL.WARM.NBMIN | Minimal number of working compressors (for WARMING state). This parameter copied to PHOS.COOL.LIQ.NBMIN when system going to WARMING state. |
| Integer | PHOS.COOL.WARM.NBMAX | Maximal number of working compressors (for WARMING state). This parameter copied to PHOS.COOL.LIQ.NBMAX when system going to WARMING state. |
| Double | PHOS.COOL.WARM.POLLTM | Polling period, seconds (for WARMING state). This parameter copied to PHOS.COOL.LIQ.POLLTM when system going to WARMING state. |
| Double | PHOS.COOL.WARM.DEADTM | Dead time after on/off, seconds (for WARMING state). This parameter copied to PHOS.COOL.LIQ.DEADTM when system going to WARMING state. |
| Integer | PHOS.COOL.WARM.NBSEN | Sensor number for cooling speed control (for WARMING state). This parameter copied to PHOS.COOL.LIQ.NBSEN when system going to WARMING state. |
| Double | PHOS.COOL.WARM.DTMAX | Maximal temperature delta for cooling speed control,°C (for WARMING state). This parameter copied to PHOS.COOL.LIQ.DTMAX when system going to WARMING state. |
| Double | PHOS.COOL.WARM.Q1 | Heat ¹1 power, % (for WARMING state). This parameter copied to PHOS.COOL.HEAT1.Q when system going to WARMING state. |
| Double | PHOS.COOL.WARM.Q2 | Heat ¹2 power, % (for WARMING state). This parameter copied to PHOS.COOL.HEAT2.Q when system going to WARMING state. |
| Double | PHOS.COOL.WARM.Q3 | Heat ¹3 power, % (for WARMING state). This parameter copied to PHOS.COOL.HEAT3.Q when system going to WARMING state. |
| Double | PHOS.COOL.DAQ.BUGS | DAQ error count. That is total number of Data Acquisition system errors (exclude OPC errors). |
| Double | PHOS.COOL.COM.BUGS | COM port errors. That is total number of errors in ADAM's RS-485 network (timeouts, CRC errors etc). |
| Integer | PHOS.COOL.INTERLOCK | Interlock on/off (1/0). Interlock means fatal error (failure) which can be dangerous for cooling plant. If interlock signal raised, cooling system execute HALT and switch off all control devices (pumps, compressors, valves), then send ALARM to DCS. Cooling can be started only after manual DCS user (shifter) RESET. |
| Integer | PHOS.COOL.CMD.CTRL | Current control mode.
CTRL=0 is OFF state. All devices switched OFF. It's absolutely safe state which correspond to FSM OFF state. CTRL=1 is HAND (manual) mode. User can switch devices manually. Correspond to FSM CALIBRATION mode. CTRL=2 is STANDBY mode. Y1, Y2 valves opened, but pumps, compressors is OFF. Correspond to FSM STANDBY mode. CTRL=3 is COOLING mode. Main operation mode to detetor cooling. Correspond to FSM COOLING and READY mode. CTRL=4 is WARMING mode. Uses for detector warming. Correspond to FSM WARMING state. |
| Integer | PHOS.COOL.CMD.BLK | Blocking (alarms) enable/disable (1/0). Alarms can be disabled only in HAND (manual) mode. |
| Integer | PHOS.COOL.BLK.NUM | Number (counter) of activeted blocks (alarms). |
| Integer | PHOS.COOL.BLK.OPT1 | Blocking options (1st part). Each bit enable/disable (1/0) some kind of alarm.
Each alarm blocks some device (XXX) by some contition (YYY), so alarms named
as "XXX by YYY". Each alarm has enable/disable flag, timeout and (maybe)
option parameter, like threshold for alarm condition.
Table of alarms listed below:
$00000001 VE1 by LPR - freon vent by Lo pressure
$00000002 VE1 by HPR - freon vent by Hi pressure
$00000004 PUMP by THR - pump by thermo relay
$00000008 PUMP by VE2 - pump by liquid vent
$00000010 PUMP by LLR - pump by Lo liquid level relay
$00000020 PUMP by HLR - pump by Hi liquid level relay
$00000040 PUMP by P3MIN - pump by Lo liquid pressure
$00000080 PUMP by P3MAX - pump by Hi liquid pressure
$00000100 PUMP by TMIN - pump by Lo liquid temperature
$00000200 PUMP by TMAX - pump by Hi liquid temperature
$00000400 COMP by THR - compressor by thermo relay
$00000800 COMP by OIL - compressor by oil level sensor
$00001000 COMP by LPR - compressor by Lo pressure relay
$00002000 COMP by HPR - compressor by Hi pressure relay
$00004000 COMP by P1MIN - compressor by Lo P1 value
$00008000 COMP by P1MAX - compressor by Hi P1 value
$00010000 COMP by P2MIN - compressor by Lo P2 value
$00020000 COMP by P2MAX - compressor by Hi P2 value
$00040000 COMP by VE1 - compressor by freon vent
$00080000 COMP by PUMP - compressor by pumps OFF
$00100000 HEAT by VE2 - heaters by liquid vent
$00200000 HEAT by PUMP - heaters by pumps OFF
$00400000 HEAT by T4MAX - heaters by Hi T4 value
$00800000 HEAT by COMP - heaters by compressors OFF
$01000000 PUMP by TPMIN - pump by Lo pump cover temp-re
$02000000 PUMP by TPMAX - pump by Hi pump cover temp-re
$04000000 VE1 by ADAMS - freon vent by ADAM errors
$08000000 LLR by REED - get LLR,HLR by reed swithes
$10000000 PUMP by LLSLO - pump by Lo Liquid Level Sensor
$20000000 PUMP by LLSHI - pump by Hi Liquid Level Sensor
$40000000 COMP by TCMIN - compressor by min. cover tempr
$80000000 COMP by TCMAX - compressor by max. cover tempr
|
| Integer | PHOS.COOL.BLK.OPT2 | Blocking options (2nd part, see above). Table of alarms listed below:
$00000001 COMP by ECV_NO - compressor by ECV NotOk
$00000002 COMP by ECV_AL - compressor by ECV ALarm
$00000004 COMP by ECV_TO - compressor by ECV TimeOut
|
| Double | PHOS.COOL.ECV.nvomo01 | ECV parameter: Suction pressure, Bar. |
| Double | PHOS.COOL.ECV.nvomo02 | ECV parameter: Suction gas temperature, °C. |
| Double | PHOS.COOL.ECV.nvomo03 | ECV parameter: Superheat, K. |
| Double | PHOS.COOL.ECV.nvomo04 | ECV parameter: Valve opening, %. |
| Double | PHOS.COOL.ECV.nvomo05 | ECV parameter: Evaporating temperature, °C. |
| Double | PHOS.COOL.ECV.nvomo06 | ECV parameter: Digital inputs, 1: Cooling demand. |
| Double | PHOS.COOL.ECV.nvomo07 | ECV parameter: Digital outputs, 1: Alarm, 2:Compressor. |
| Double | PHOS.COOL.ECV.nvomo08 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo09 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo10 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo11 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo12 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo13 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo14 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo15 | ECV parameter: Superheat setpoint, K. |
| Double | PHOS.COOL.ECV.nvomo16 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo17 | ECV parameter: at the moment, unknown. |
| Double | PHOS.COOL.ECV.nvomo18 | ECV parameter: at the moment, unknown. |
| Integer | PHOS.COOL.WDT.VE1_LPR | Alarm timeout: Block VE1 by LPR This alarm blocks freon (R404A) vent Y1 if Low Pressure Relay connected during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: freon leak. |
| Integer | PHOS.COOL.WDT.VE1_HPR | Alarm timeout:Block VE1 by HPR This alarm blocks freon (R404A) vent Y1 if High Pressure Relay connected during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: water cooling is off (no heat removed from water condensor). |
| Integer | PHOS.COOL.WDT.PUMP_THR | Alarm timeout: Block PUMP by THR This alarm blocks pump (to flow C6F14) if THermo Relay connected during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: pump overload (overheat, overcurrent etc). |
| Integer | PHOS.COOL.WDT.PUMP_VE2 | Alarm timeout: Block PUMP by VE2 This alarm blocks pump (to flow C6F14) if Y2 vent (for cooling liquid) closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: pump switch on when Y2 vent closed (in manual mode). That is forbidden operation mode. |
| Integer | PHOS.COOL.WDT.PUMP_LLR | Alarm timeout: Block PUMP by LLR This alarm blocks pump (to flow C6F14) if Low Level Relay closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: low level of cooling liquid in receiver tank (empty tank, liquid leak). At the moment this relay doesn't work properly, so it's switched off. |
| Integer | PHOS.COOL.WDT.PUMP_HLR | Alarm timeout: Block PUMP by HLR This alarm blocks pump (to flow C6F14) if High Level Relay closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: high level of cooling liquid in receiver tank (full tank, overload). At the moment this relay doesn't work properly, so it's switched off. |
| Integer | PHOS.COOL.WDT.PUMP_P3MIN | Alarm timeout: Block PUMP by P3MIN This alarm blocks pump (to flow C6F14) if liquid pressure less then threshold during timeout, i.e. P3 < P3min. Negative timeout cause fatal Intelock. Possible reason of alarm: no liquid (liquid leak) or sensor failure. |
| Integer | PHOS.COOL.WDT.PUMP_P3MAX | Alarm timeout: Block PUMP by P3MAX This alarm blocks pump (to flow C6F14) if liquid pressure greater then threshold during timeout, i.e. P3 > P3max. Negative timeout cause fatal Intelock. Possible reason of alarm: closed vent or "thrombus" in cooling liqud's pipes or sensor failure. |
| Integer | PHOS.COOL.WDT.PUMP_TMIN | Alarm timeout: Block PUMP by TMIN This alarm blocks pump (to flow C6F14) if liquid temperature less then threshold during timeout, i.e. T1 < Tmin. Negative timeout cause fatal Intelock. Possible reason of alarm: cooling liqud underheat (for example, wrong control parameter's setup). |
| Integer | PHOS.COOL.WDT.PUMP_TMAX | Alarm timeout: Block PUMP by TMAX This alarm blocks pump (to flow C6F14) if liquid temperature greater then threshold during timeout, i.e. T1 > Tmax. Negative timeout cause fatal Intelock. Possible reason of alarm: cooling liqud overheat (for example, incufficient compressor's power). |
| Integer | PHOS.COOL.WDT.COMP_THR | Alarm timeout: Block COMP by THR This alarm blocks compressor (to flow freon R404A) if THermo Relay closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: compressor overload (overheat, overcurrent etc). |
| Integer | PHOS.COOL.WDT.COMP_OIL | Alarm timeout: Block COMP by OIL This alarm blocks compressor (to flow freon R404A) if OIL low level relay closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: compressor's oil low level (oil system failure or compressor frozen). |
| Integer | PHOS.COOL.WDT.COMP_LPR | Alarm timeout: Block COMP by LPR This alarm blocks compressor (to flow freon R404A) if Low Pressure Relay closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: insufficient freon pressure (leak), freon ECV valve closed (with working compressors) or wrong control parameter's setup. |
| Integer | PHOS.COOL.WDT.COMP_HPR | Alarm timeout: Block COMP by HPR This alarm blocks compressor (to flow freon R404A) if High Pressure Relay closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: freon overpressure due to freon overheat, when water condensor don't work (no water flow). |
| Integer | PHOS.COOL.WDT.COMP_P1MIN | Alarm timeout: Block COMP by P1MIN This alarm blocks compressor (to flow freon R404A) if freon condensator (discharge) pressure less then threshold during timeout, i.e. P1 < P1min. Negative timeout cause fatal Intelock. Possible reason of alarm: insufficient freon pressure (leak). |
| Integer | PHOS.COOL.WDT.COMP_P1MAX | Alarm timeout: Block COMP by P1MAX This alarm blocks compressor (to flow freon R404A) if freon evaporator (suction) pressure greater then threshold during timeout, i.e. P1 > P1max. Negative timeout cause fatal Intelock. Possible reason of alarm: freon overpressure due to freon overheat, when water condensor doesn't work (no water flow). |
| Integer | PHOS.COOL.WDT.COMP_P2MIN | Alarm timeout: Block COMP by P2MIN This alarm blocks compressor (to flow freon R404A) if freon evaporator (suction) pressure less then threshold during timeout, i.e. P2 < P2min. Negative timeout cause fatal Intelock. Possible reason of alarm: insufficient freon pressure (leak), freon ECV valve closed (with working compressors) or wrong control parameter's setup. |
| Integer | PHOS.COOL.WDT.COMP_P2MAX | Alarm timeout: Block COMP by P2MAX This alarm blocks compressor (to flow freon R404A) if freon evaporator (suction) pressure less then threshold during timeout, i.e. P2 > P2max. Negative timeout cause fatal Intelock. Possible reason of alarm: freon overpressure (for example, no water cooling). |
| Integer | PHOS.COOL.WDT.COMP_VE1 | Alarm timeout: Block COMP by VE1 This alarm blocks compressor (to flow freon R404A) if freon valve Y1 closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: compressor switch on when freon valve closed. This operation mode forbidden. |
| Integer | PHOS.COOL.WDT.COMP_PUMP | Alarm timeout: Block COMP by PUMP This alarm blocks compressor (to flow freon R404A) if pump switched OFF during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: compressor switch on when pump is off. This operation mode forbidden. |
| Integer | PHOS.COOL.WDT.HEAT_VE2 | Alarm timeout: Block HEAT by VE2 This alarm blocks heater if cooling liquid valve Y2 closed during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: heater switch on when cooling liquid valve closed. This operation mode forbidden. |
| Integer | PHOS.COOL.WDT.HEAT_PUMP | Alarm timeout: Block HEAT by PUMP This alarm blocks heater if pump switched OFF during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: heater switch on when pump is off. This operation mode forbidden. |
| Integer | PHOS.COOL.WDT.HEAT_T4MAX | Alarm timeout: Block HEAT by T4MAX This alarm blocks heater 1 if T4 temperature is over threshold during timeout, i.e. T4 > T4max. Negative timeout cause fatal Intelock. Possible reason of alarm: heater 1 is overheat. |
| Integer | PHOS.COOL.WDT.HEAT_COMP | Alarm timeout: Block HEAT by COMP This alarm blocks heater if compressors switched OFF during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: heater switch on when compressors is off. This operation mode forbidden. |
| Integer | PHOS.COOL.WDT.PUMP_TPMIN | Alarm timeout: Block PUMP by TPMIN This alarm blocks pump (1,2) if pump cover temperature (T8,T9) less then threshold. Negative timeout cause fatal Intelock. Possible reason of alarm: pump frozen. |
| Integer | PHOS.COOL.WDT.PUMP_TPMAX | Alarm timeout: Block PUMP by TPMAX This alarm blocks pump (1,2) if pump cover temperature (T8,T9) greater then threshold. Negative timeout cause fatal Intelock. Possible reason of alarm: pump overheat. |
| Integer | PHOS.COOL.WDT.VE1_ADAMS | Alarm timeout: Block VE1 by ADAMS This alarm blocks freon vent Y1 if ADAM's errors coming during timeout. Negative timeout cause fatal Intelock. Possible reason of alarm: ADAM's failure or RS-485 network connection lost. ADAM's is RS-485 remote network data acquisition modules of I-7000 seria produced by ICP-DAS company. |
| Integer | PHOS.COOL.WDT.PUMP_LLSLO | Alarm timeout: Block PUMP by LLSLO This alarm blocks pumps if cooling liquid (C6F14) level in receiver tank less then threshold during timeout, i.e. LLS.VL < LLS.LO. Negative timeout cause fatal Intelock. Possible reason of alarm: incufficient liquid level (leak), receiver tank is empty. |
| Integer | PHOS.COOL.WDT.PUMP_LLSHI | Alarm timeout: Block PUMP by LLSHI This alarm blocks pumps if cooling liquid (C6F14) level in receiver tank greater then threshold during timeout, i.e. LLS.VL > LLS.HI. Negative timeout cause fatal Intelock. Possible reason of alarm: receiver tank is overfull. |
| Integer | PHOS.COOL.WDT.COMP_TCMIN | Alarm timeout: Block COMP by TCMIN This alarm blocks compressor (to flow freon R404A) if compressor cover temperature (T11..T14) less then threshold during timeout, i.e. T11..T14 < Tcmin. Negative timeout cause fatal Intelock. Possible reason of alarm: compressor frozen. |
| Integer | PHOS.COOL.WDT.COMP_TCMAX | Alarm timeout: Block COMP by TCMAX This alarm blocks compressor (to flow freon R404A) if compressor cover temperature (T11..T14) greater then threshold during timeout, i.e. T11..T14 > Tcmax. Negative timeout cause fatal Intelock. Possible reason of alarm: compressor overheat. |
| Integer | PHOS.COOL.WDT.COMP_ECV | Alarm timeout: Block COMP by ECV This alarm blocks compressor (to flow freon R404A) if ECV controller raise alarm during timeout, i.e. ECV alarm flags is non-zero. Negative timeout cause fatal Intelock. Possible reason of alarm: ECV failure or network connection lost on LAN-2. Note that alidcscom252 cooling server uses LAN-1 for DIM connection, and LAN-2 - for ECV connection. |
| Integer | PHOS.COOL.WDT.VE1_POWER | Alarm timeout: Block VE1 by POWER This alarm blocks VE1 (vent for freon R404A) if general power cut (380V) found during timeout, i.e. POWER flag is zero. Negative timeout cause fatal Intelock. Possible reason of alarm: general power cut. |
| Integer | PHOS.COOL.WDT.VE1_WATER | Alarm timeout: Block VE1 by WATER This alarm blocks VE1 (vent for freon R404A) if water flow rate absence found during timeout, i.e. WATER flag is zero. Negative timeout cause fatal Intelock. Possible reason of alarm: general water failure. |
| Integer | PHOS.FSM.FSM | Enable/disable (1/0) PHOS cooling control thru FSM. |
| Integer | PHOS.FSM.DIM | Enable/disable (1/0) FSM control thru DIM. |
| Integer | PHOS.FSM.STATE | Finite State Machine state:
|
| Char | PHOS.FSM.ACTION | Command coming from PVSS level. Available next commands: SWITCH_OFF, GO_STANDBY, RESET, CALIBRATION, COOLING, WARMING, GO_READY. See picture above. |
| Double | PHOS.COOL.PCPS.V1 | Voltage, in Volts, of 1-st channel of fault protected PC Power Supply. |
| Double | PHOS.COOL.PCPS.V2 | Voltage, in Volts, of 2-nd channel of fault protected PC Power Supply. |
| Integer | PHOS.COOL.PCPS.S1 | Status (Voltage>15V) of 1-st channel of fault protected PC Power Supply. |
| Integer | PHOS.COOL.PCPS.S2 | Status (Voltage>15V) of 2-nd channel of fault protected PC Power Supply. |
| Double | PHOS.MATR.PWOn.T_m | PWOn temperature by Ni100 or Pt100 sensor m, n=0..5, m=0..23. |
| Integer | PHOS.MATR.PWOn.WDT_m | Watchdog status (0=fail,1=Ok) of PWOn temperature by Ni100 or Pt100 sensor m, n=0..5, m=0..23. |
| Double | PHOS.MATR.FEEn.T_m | FEEn temperature by Ni100 or Pt100 sensor m, n=0..5, m=0..7. |
| Double | PHOS.MATR.FEEn.T2_m | Temperature by humidity sensor m in module n, n=0..5, m=0..6. (H0,H2):FEE, (H1,H2,H3):PWO, (H4,H6):unused. |
| Double | PHOS.MATR.FEEn.H_m | Humidity (%) by humidity sensor m in module n, n=0..5, m=0..6. (H0,H2):FEE, (H1,H2,H3):PWO, (H4,H6):unused. |
| Integer | PHOS.MATR.FEEn.WDT_m | Watchdog status (0=fail,1=Ok) of sensor k, n=0..5, m=0..21.
m=0..7 corresponds to sensors PHOS.MATR.FEEn.T_k, k=m=0..7. m=8..14 corresponds to sensors PHOS.MATR.FEEn.T2_k, k=m-8=0..6. m=15..21 corresponds to sensors PHOS.MATR.FEEn.H_k, k=m-15=0..6. |
| Double | PHOS.MATR.PWO1.T_0 | PWO1 temperature by Pt100 sensor 0 - PTM16. ELMB7, Slot2, Pin29-32, R15. |
| Integer | PHOS.MATR.PWO1.WDT_0 | Watchdog for PHOS.MATR.PWO1.T_0 |
| Service Name (Cmnd,Info) | Content (list of tags) |
| ALICE/PHOS/COOLING/COOL/CLICK | PHOS.COOL.CLICK Command service for remote clients. |
| ALICE/PHOS/COOLING/COOL/NOTIFY | PHOS.COOL.NOTIFY |
| ALICE/PHOS/COOLING/COOL/ALARM_LOG | PHOS.COOL.ALARM_LOG |
| ALICE/PHOS/COOLING/COOL/CONSOLE | PHOS.COOL.CONSOLE Command service (Char) to setup control parameters. Service should contanins command lines (CR,LF separated). Next commands available:
|
| ALICE/PHOS/COOLING/COOL/HOST_TIME+HOST_INFO | PHOS.COOL.HOST_TIME, PHOS.COOL.HOST_INFO |
| ALICE/PHOS/COOLING/COOL/DAQ/BUGS | PHOS.COOL.DAQ.BUGS |
| ALICE/PHOS/COOLING/COOL/COM/BUGS | PHOS.COOL.COM.BUGS |
| ALICE/PHOS/COOLING/COOL/P1 | PHOS.COOL.P1 |
| ALICE/PHOS/COOLING/COOL/P2 | PHOS.COOL.P2 |
| ALICE/PHOS/COOLING/COOL/P3 | PHOS.COOL.P3 |
| ALICE/PHOS/COOLING/COOL/T1 | PHOS.COOL.T1 |
| ALICE/PHOS/COOLING/COOL/T2 | PHOS.COOL.T2 |
| ALICE/PHOS/COOLING/COOL/T3 | PHOS.COOL.T3 |
| ALICE/PHOS/COOLING/COOL/T4 | PHOS.COOL.T4 |
| ALICE/PHOS/COOLING/COOL/T5 | PHOS.COOL.T5 |
| ALICE/PHOS/COOLING/COOL/T6 | PHOS.COOL.T6 |
| ALICE/PHOS/COOLING/COOL/T7 | PHOS.COOL.T7 |
| ALICE/PHOS/COOLING/COOL/T8 | PHOS.COOL.T8 |
| ALICE/PHOS/COOLING/COOL/T9 | PHOS.COOL.T9 |
| ALICE/PHOS/COOLING/COOL/T10 | PHOS.COOL.T10 |
| ALICE/PHOS/COOLING/COOL/T11 | PHOS.COOL.T11 |
| ALICE/PHOS/COOLING/COOL/T12 | PHOS.COOL.T12 |
| ALICE/PHOS/COOLING/COOL/T13 | PHOS.COOL.T13 |
| ALICE/PHOS/COOLING/COOL/T14 | PHOS.COOL.T14 |
| ALICE/PHOS/COOLING/COOL/T15 | PHOS.COOL.T15 |
| ALICE/PHOS/COOLING/COOL/T16 | PHOS.COOL.T16 |
| ALICE/PHOS/COOLING/COOL/T17 | PHOS.COOL.T17 |
| ALICE/PHOS/COOLING/COOL/T18 | PHOS.COOL.T18 |
| ALICE/PHOS/COOLING/COOL/T19 | PHOS.COOL.T19 |
| ALICE/PHOS/COOLING/COOL/T20 | PHOS.COOL.T20 |
| ALICE/PHOS/COOLING/COOL/T21 | PHOS.COOL.T21 |
| ALICE/PHOS/COOLING/COOL/T22 | PHOS.COOL.T22 |
| ALICE/PHOS/COOLING/ COOL/COMP1/ENB+POW+WTM+THR+OIL+LPR+HPR |
PHOS.COOL.COMP1.ENB, PHOS.COOL.COMP1.POW, PHOS.COOL.COMP1.WTM, PHOS.COOL.COMP1.THR, PHOS.COOL.COMP1.OIL, PHOS.COOL.COMP1.LPR, PHOS.COOL.COMP1.HPR |
| ALICE/PHOS/COOLING/ COOL/COMP2/ENB+POW+WTM+THR+OIL+LPR+HPR |
PHOS.COOL.COMP2.ENB, PHOS.COOL.COMP2.POW, PHOS.COOL.COMP2.WTM, PHOS.COOL.COMP2.THR, PHOS.COOL.COMP2.OIL, PHOS.COOL.COMP2.LPR, PHOS.COOL.COMP2.HPR |
| ALICE/PHOS/COOLING/ COOL/COMP3/ENB+POW+WTM+THR+OIL+LPR+HPR |
PHOS.COOL.COMP3.ENB, PHOS.COOL.COMP3.POW, PHOS.COOL.COMP3.WTM, PHOS.COOL.COMP3.THR, PHOS.COOL.COMP3.OIL, PHOS.COOL.COMP3.LPR, PHOS.COOL.COMP3.HPR |
| ALICE/PHOS/COOLING/ COOL/COMP4/ENB+POW+WTM+THR+OIL+LPR+HPR |
PHOS.COOL.COMP4.ENB, PHOS.COOL.COMP4.POW, PHOS.COOL.COMP4.WTM, PHOS.COOL.COMP4.THR, PHOS.COOL.COMP4.OIL, PHOS.COOL.COMP4.LPR, PHOS.COOL.COMP4.HPR |
| ALICE/PHOS/COOLING/ COOL/PUMP1/ENB+POW+WTM+THR |
PHOS.COOL.PUMP1.ENB, PHOS.COOL.PUMP1.POW, PHOS.COOL.PUMP1.WTM, PHOS.COOL.PUMP1.THR |
| ALICE/PHOS/COOLING/ COOL/PUMP2/ENB+POW+WTM+THR |
PHOS.COOL.PUMP2.ENB, PHOS.COOL.PUMP2.POW, PHOS.COOL.PUMP2.WTM, PHOS.COOL.PUMP2.THR |
| ALICE/PHOS/COOLING/COOL/FREON/ENB+VE1+LPR+HPR | PHOS.COOL.FREON.ENB, PHOS.COOL.FREON.VE1, PHOS.COOL.FREON.LPR, PHOS.COOL.FREON.HPR |
| ALICE/PHOS/COOLING/COOL/FREON/ECV | PHOS.COOL.FREON.ECV |
| ALICE/PHOS/COOLING/ COOL/LIQ/ENB+VE2+HLR+LLR+REED+TMIN+TMAX+ TSTAB+DELTA+NBSEN+DTMAX |
PHOS.COOL.LIQ.ENB, PHOS.COOL.LIQ.VE2, PHOS.COOL.LIQ.HLR, PHOS.COOL.LIQ.LLR, PHOS.COOL.LIQ.REED, PHOS.COOL.LIQ.TMIN, PHOS.COOL.LIQ.TMAX, PHOS.COOL.LIQ.TSTAB, PHOS.COOL.LIQ.DELTA, PHOS.COOL.LIQ.NBSEN, PHOS.COOL.LIQ.DTMAX, |
| ALICE/PHOS/COOLING/COOL/LIQ/TSENS+TGOAL+TAVER | PHOS.COOL.LIQ.TSENS, PHOS.COOL.LIQ.TGOAL, PHOS.COOL.LIQ.TAVER |
| ALICE/PHOS/COOLING/COOL/LIQ/CAVER+NAVER | PHOS.COOL.LIQ.CAVER, PHOS.COOL.LIQ.NAVER |
| ALICE/PHOS/COOLING/COOL/LIQ/NCOMP | PHOS.COOL.LIQ.NCOMP |
| ALICE/PHOS/COOLING/COOL/LIQ/NFDBK+TFDBK | PHOS.COOL.LIQ.NFDBK, PHOS.COOL.LIQ.TFDBK |
| ALICE/PHOS/COOLING/COOL/LIQ/LLS/MM+PC+VL | PHOS.COOL.LIQ.LLS.MM, PHOS.COOL.LIQ.LLS.PC, PHOS.COOL.LIQ.LLS.VL |
| ALICE/PHOS/COOLING/ COOL/LIQ/LLS/LO+HI |
PHOS.COOL.LIQ.LLS.LO, PHOS.COOL.LIQ.LLS.HI |
| ALICE/PHOS/COOLING/COOL/FAN/ENB+POW+WTM+TON | PHOS.COOL.FAN.ENB, PHOS.COOL.FAN.POW, PHOS.COOL.FAN.WTM, PHOS.COOL.FAN.TON |
| ALICE/PHOS/COOLING/COOL/FAN1/ENB+POW | PHOS.COOL.FAN1.ENB, PHOS.COOL.FAN1.POW |
| ALICE/PHOS/COOLING/COOL/FAN2/ENB+POW | PHOS.COOL.FAN2.ENB, PHOS.COOL.FAN2.POW |
| ALICE/PHOS/COOLING/COOL/FAN3/ENB+POW | PHOS.COOL.FAN3.ENB, PHOS.COOL.FAN3.POW |
| ALICE/PHOS/COOLING/COOL/FAN4/ENB+POW | PHOS.COOL.FAN4.ENB, PHOS.COOL.FAN4.POW |
| ALICE/PHOS/COOLING/ COOL/HEAT1/ENB+POW+SSR+PER+Q+QMAX |
PHOS.COOL.HEAT1.ENB, PHOS.COOL.HEAT1.POW, PHOS.COOL.HEAT1.SSR, PHOS.COOL.HEAT1.PER, PHOS.COOL.HEAT1.Q, PHOS.COOL.HEAT1.QMAX |
| ALICE/PHOS/COOLING/ COOL/HEAT2/ENB+POW+SSR+PER+Q+QMAX |
PHOS.COOL.HEAT2.ENB, PHOS.COOL.HEAT2.POW, PHOS.COOL.HEAT2.SSR, PHOS.COOL.HEAT2.PER, PHOS.COOL.HEAT2.Q, PHOS.COOL.HEAT2.QMAX |
| ALICE/PHOS/COOLING/ COOL/HEAT3/ENB+POW+SSR+PER+Q+QMAX |
PHOS.COOL.HEAT3.ENB, PHOS.COOL.HEAT3.POW, PHOS.COOL.HEAT3.SSR, PHOS.COOL.HEAT3.PER, PHOS.COOL.HEAT3.Q, PHOS.COOL.HEAT3.QMAX |
| ALICE/PHOS/COOLING/ COOL/COMP/P1MIN+P1MAX+P2MIN+P2MAX+ NBMIN+NBMAX+POLLTM+DEADTM |
PHOS.COOL.COMP.P1MIN, PHOS.COOL.COMP.P1MAX, PHOS.COOL.COMP.P2MIN, PHOS.COOL.COMP.P2MAX, PHOS.COOL.COMP.NBMIN, PHOS.COOL.COMP.NBMAX, PHOS.COOL.COMP.POLLTM, PHOS.COOL.COMP.DEADTM |
| ALICE/PHOS/COOLING/COOL/COMP/TCMIN+TCMAX+CYCLE | PHOS.COOL.COMP.TCMIN, PHOS.COOL.COMP.TCMAX, PHOS.COOL.COMP.CYCLE |
| ALICE/PHOS/COOLING/ COOL/PUMP/P3MIN+P3MAX+TPMIN+TPMAX+CYCLE |
PHOS.COOL.PUMP.P3MIN, PHOS.COOL.PUMP.P3MAX, PHOS.COOL.PUMP.TPMIN, PHOS.COOL.PUMP.TPMAX, PHOS.COOL.PUMP.CYCLE |
| ALICE/PHOS/COOLING/COOL/HEATS/T4MAX | PHOS.COOL.HEATS.T4MAX |
| ALICE/PHOS/COOLING/COOL/INTERLOCK | PHOS.COOL.INTERLOCK |
| ALICE/PHOS/COOLING/COOL/CMD/CTRL | PHOS.COOL.CMD.CTRL |
| ALICE/PHOS/COOLING/COOL/CMD/BLK | PHOS.COOL.CMD.BLK |
| ALICE/PHOS/COOLING/COOL/BLK/NUM | PHOS.COOL.BLK.NUM |
| ALICE/PHOS/COOLING/COOL/BLK/OPT1+OPT2 | PHOS.COOL.BLK.OPT1, PHOS.COOL.BLK.OPT2 |
| ALICE/PHOS/COOLING/ STBY/TSTAB+DELTA+NBMIN+NBMAX+POLLTM+DEADTM+ NBSEN+DTMAX+Q1+Q2+Q3 |
PHOS.COOL.STBY.TSTAB, PHOS.COOL.STBY.DELTA, PHOS.COOL.STBY.NBMIN, PHOS.COOL.STBY.NBMAX, PHOS.COOL.STBY.POLLTM, PHOS.COOL.STBY.DEADTM, PHOS.COOL.STBY.NBSEN, PHOS.COOL.STBY.DTMAX, PHOS.COOL.STBY.Q1, PHOS.COOL.STBY.Q2, PHOS.COOL.STBY.Q3 |
| ALICE/PHOS/COOLING/ COOL/TSTAB+DELTA+NBMIN+NBMAX+POLLTM+DEADTM+ NBSEN+DTMAX+Q1+Q2+Q3 |
PHOS.COOL.COOL.TSTAB, PHOS.COOL.COOL.DELTA, PHOS.COOL.COOL.NBMIN, PHOS.COOL.COOL.NBMAX, PHOS.COOL.COOL.POLLTM, PHOS.COOL.COOL.DEADTM, PHOS.COOL.COOL.NBSEN, PHOS.COOL.COOL.DTMAX, PHOS.COOL.COOL.Q1, PHOS.COOL.COOL.Q2, PHOS.COOL.COOL.Q3 |
| ALICE/PHOS/COOLING/ WARM/TSTAB+DELTA+NBMIN+NBMAX+POLLTM+DEADTM+ NBSEN+DTMAX+Q1+Q2+Q3 |
PHOS.COOL.WARM.TSTAB, PHOS.COOL.WARM.DELTA, PHOS.COOL.WARM.NBMIN, PHOS.COOL.WARM.NBMAX, PHOS.COOL.WARM.POLLTM, PHOS.COOL.WARM.DEADTM, PHOS.COOL.WARM.NBSEN, PHOS.COOL.WARM.DTMAX, PHOS.COOL.WARM.Q1, PHOS.COOL.WARM.Q2, PHOS.COOL.WARM.Q3 |
| ALICE/PHOS/COOLING/ COOL/ECV/DISPLAY/NVOMO01-18 |
PHOS.COOL.ECV.nvomo01, PHOS.COOL.ECV.nvomo02, PHOS.COOL.ECV.nvomo03, PHOS.COOL.ECV.nvomo04, PHOS.COOL.ECV.nvomo05, PHOS.COOL.ECV.nvomo06, PHOS.COOL.ECV.nvomo07, PHOS.COOL.ECV.nvomo08, PHOS.COOL.ECV.nvomo09, PHOS.COOL.ECV.nvomo10, PHOS.COOL.ECV.nvomo11, PHOS.COOL.ECV.nvomo12, PHOS.COOL.ECV.nvomo13, PHOS.COOL.ECV.nvomo14, PHOS.COOL.ECV.nvomo15, PHOS.COOL.ECV.nvomo16, PHOS.COOL.ECV.nvomo17, PHOS.COOL.ECV.nvomo18 |
| ALICE/PHOS/COOLING/ COOL/WDT/VE1_LPR+VE1_HPR+PUMP_THR+PUMP_VE2+ PUMP_LLR+PUMP_HLR+PUMP_P3MIN+PUMP_P3MAX+ PUMP_TMIN+PUMP_TMAX |
PHOS.COOL.WDT.VE1_LPR, PHOS.COOL.WDT.VE1_HPR, PHOS.COOL.WDT.PUMP_THR, PHOS.COOL.WDT.PUMP_VE2, PHOS.COOL.WDT.PUMP_LLR, PHOS.COOL.WDT.PUMP_HLR, PHOS.COOL.WDT.PUMP_P3MIN, PHOS.COOL.WDT.PUMP_P3MAX, PHOS.COOL.WDT.PUMP_TMIN, PHOS.COOL.WDT.PUMP_TMAX |
| ALICE/PHOS/COOLING/ COOL/WDT/COMP_THR+COMP_OIL+ COMP_LPR+COMP_HPR+COMP_P1MIN+COMP_P1MAX+ COMP_P2MIN+COMP_P2MAX+ COMP_VE1+COMP_PUMP |
PHOS.COOL.WDT.COMP_THR, PHOS.COOL.WDT.COMP_OIL, PHOS.COOL.WDT.COMP_LPR, PHOS.COOL.WDT.COMP_HPR, PHOS.COOL.WDT.COMP_P1MIN, PHOS.COOL.WDT.COMP_P1MAX, PHOS.COOL.WDT.COMP_P2MIN, PHOS.COOL.WDT.COMP_P2MAX, PHOS.COOL.WDT.COMP_VE1, PHOS.COOL.WDT.COMP_PUMP |
| ALICE/PHOS/COOLING/ COOL/WDT/HEAT_VE2+HEAT_PUMP+ HEAT_T4MAX+HEAT_COMP+PUMP_TPMIN+PUMP_TPMAX+ VE1_ADAMS+PUMP_LLSLO+PUMP_LLSHI |
PHOS.COOL.WDT.HEAT_VE2, PHOS.COOL.WDT.HEAT_PUMP, PHOS.COOL.WDT.HEAT_T4MAX, PHOS.COOL.WDT.HEAT_COMP, PHOS.COOL.WDT.PUMP_TPMIN, PHOS.COOL.WDT.PUMP_TPMAX, PHOS.COOL.WDT.VE1_ADAMS, PHOS.COOL.WDT.PUMP_LLSLO, PHOS.COOL.WDT.PUMP_LLSHI |
| ALICE/PHOS/COOLING/ COOL/WDT/COMP_TCMIN+COMP_TCMAX+COMP_ECV |
PHOS.COOL.WDT.COMP_TCMIN, PHOS.COOL.WDT.COMP_TCMAX, PHOS.COOL.WDT.COMP_ECV |
| ALICE/PHOS/COOLING/ COOL/FREON/POWER+WATER |
PHOS.COOL.FREON.POWER, PHOS.COOL.FREON.WATER |
| ALICE/PHOS/COOLING/ COOL/WDT/VE1_POWER+VE1_WATER |
PHOS.COOL.WDT.VE1_POWER, PHOS.COOL.WDT.VE1_WATER |
| ALICE/PHOS/COOLING/ COOL/WATER/FLOW |
PHOS.COOL.WATER.FLOW |
| ALICE/PHOS/COOLING/ COOL/WATER/FEDGE+PEDGE |
PHOS.COOL.WATER.FEDGE, PHOS.COOL.WATER.PEDGE |
| ALICE/PHOS/COOLING/ COOL/PCPS/V1+V2+S1+S2 |
PHOS.COOL.PCPS.V1, PHOS.COOL.PCPS.V2, PHOS.COOL.PCPS.S1, PHOS.COOL.PCPS.S2. |
| , , | |
| , , |