How to use cooling system.
Contents
Preparation for cooling.
- Connect Cooling hoses to the module.
- Put in order thermo-insulation of cooling system.
- Close Confluent valve of the system.
- Flood the cooling liquid to the system. You should do it by special RED funnel.
- Connect Data cable RS-232 (short) from PC to adapter.
Connect Data cable RS-485 (long) from adapter to the cooling system
Connect Data cable CAN from PC to the ELMB.
Connect power supplay for the ELMB and for the adapter. See scheme:
- Connect POWER cables ~220V to supplay control system of cooling mashine and to supplay
heaters ih FEE volume.
- Switch CLUSTER SWITCH to position ON:
- Connect POWER cable ~380V to supplay the cooling mashine.
- Switch COMPRESSOR SWITCH and SOLENOID SWITCH to position ON (They are at the side of the cooling table):
- RUN the program of cooling system. You can do it by icon
,
which is placed on the Desktop or on the Quick Launch of the Taskbar. Measurement and control
start automatically.
- So you can start cooling...
How to find symbolic circuits.
This is the screenshot of the program of cooling system. So when the program starts it has view like this:
As you see, the control of cooling system is realized by symbolic circuits. Ich of them has unique name.
If you do not see on the screen symbolic circuit, which you need to use,
you can find it in the following way:
- On the top panel of program
press the button
.
So on the top left corner you can see the panel which is named "DAQ-SYSTEM".
- On the panel "DAQ-SYSTEM"
press the button
.
- After that in the menu Open mnemonic window:
you should choose the symbolic circuit, which you need.
Cooling.
To start cooling you should:
- In symbolic circuit PHOS.FSM.CTRL:
switch OFF the sensor
.
- In symbolic circuit PHOS.COOL.CTRL:
press the button
.
After that pump, compressor cooling and temperature stabilization will switch
ON automatically.
- On filds
set maximum (-23.5) and minimum (-26) temperatures of cooling liquid. So the average temperature of cooling liquid
will be between MAX and MIN. Please, be careful during settings, because the gradient
between the temperature of cooling liquid and the temperature in the PWO matrix has to be less
than 25 degrees.
- You should to see to the matrix temperature that to decrease the temperature of cooling liquid.
- Cooling liquid has a big temperature coefficient of expansion.
SO it is important - during cooling or warming processes you have to equalize
pressure in the cooling system and atmosphere pressure. You should do it by short-time opening the stopper
of the input flood pipe. It would be better if you put cable binder between the input pipe and stopper
during cooling or warming processes. See the picture:
- The current temperature of the cooling liquid you can see on the sensor:
.
To see the temperature curve press this sensor.
- To see the temperature distribution of the PWO matrix you should choose the symbolyc circuit
PHOS.PWO2.CTRL:
.
- To see the temperature curves press sensors:
- To switch ON the heater in FEE volume:
- In symbolic circuit PHOS.FEE2.CTRL:
press the button
.
- In fild
set the temperature of stabilization FEE volume (+31).
- In fild
set the off-duty factor of heater (50).
- So the temperature in FEE volume will be supported automatically.
- The current temperature of the FEE volume you can see on the sensor:
.
To see the temperature curve press this sensor.
- To see the temperature distribution of the FEE volume matrix you should choose the symbolyc circuit
PHOS.FEE2.VIEW:
.
- To see the temperature curves press sensors:
Warming.
- To warm the module firts of all you should switch OFF the cooling machine
- To do it in symbolic circuit PHOS.COOL.CTRL:
press buttons
and
.
- To warm the cooling liquid quickly, on the symbolic circuit PHOS.HEAT.CTRL:
press the button
.
- In fild
set the temperature of cooling liquid. Please, be careful during settings, because the gradient
between the temperature of cooling liquid and the temperature in the PWO matrix has to be less
than 25 degrees.
- You should to see to the matrix temperature that to increase the temperature of cooling liquid.
- In fild
set the off-duty factor of heater (30).
- So the temperature of cooling liquid will be supported automatically.
- The current temperature of cooling liquid you can see on the sensor:
.
To see the temperature curve press this sensor.
- Cooling liquid has a big temperature coefficient of expansion.
SO it is important - during cooling or warming processes you have to equalize
pressure in the cooling system and atmosphere pressure. You should do it by short-time opening the stopper
of the input flood pipe. It would be better if you put cable binder between the input pipe and stopper
during cooling or warming processes. See the picture:
Switching OFF the cooling system.
- Press the button:
in the symbolic circuit PHOS.FEE2.CTRL
and the button:
in the symbolic circuit PHOS.HEAT.CTRL
to switch OFF all heaters.
- Stop control and measurements by the button
in the panel DAQ-SYSTEM:
- So you can end the program by the button
on the top panel of program:
- Switch OFF the PC.
- Disonnect Data cable RS-232 (short) from PC to adapter.
Disconnect Data cable RS-485 (long) from adapter to the cooling system
Disconnect Data cable CAN from PC to the ELMB.
Disconnect power supplay for the ELMB and for the adapter. See scheme:
- Switch CLUSTER SWITCH to position OFF:
- Disconnect POWER cables ~220V to supplay control system of cooling mashine and to supplay
heaters ih FEE volume.
- Switch COMPRESSOR SWITCH and SOLENOID SWITCH to position OFF:
- Disconnect POWER cable ~380V to supplay the cooling mashine.
- Prepare volumes for cooling liquid.
- Lift module to the highest position.
- Open the stopper in the input flood pipe of the system.
- Open Confluent valve of the system and dump cooling liquid to special volumes.